82
saia-pcd.com
PCD
1
E-Line
Automation stations –
E-Line
Saia PCD1.H108S-F00 (S0 pulse counter with 8E)*
The PCD1.H108S-F00 modules can also record the classic S0 pulses and temperatures of the PT1000 sensors
directly, and evaluate the SBC's own unidirectional S0+ protocol, which is sent via the S0 output. The inputs of
the S0 pulse counter can be directly connected to PT1000 temperature sensors or also to the S0+ protocol.
The medium applied is detected automatically. The S0 pulse counter PCD1.H108S-F00 enables an efficient
transfer, evaluation and forwarding of energy data without additional complicated coupling modules directly
to the S-monitoring solutions from SBC.
1.5.5
Communication and counter modules
System properties
8 multi-functional inputs
Direct connection of PT1000 temperature sensors
Reading of S0 pulses
Reading of the unidirectional protocol S0+
Automatic integration in the S-monitoring system
Galvanic isolation between supply, bus and inputs
Pluggable terminal blocks protected by covers
Status LEDs at the front
NFC interface
Configuration and control using FBoxes
Connection example
Inputs
8 multi-functional inputs
I1-I4: PT1000 inputs, –30…100°C, 0.5 °C precision I1-I8: S0 inputs in accordance with IEC62053−31 (S0 standard)
The inputs can also read the SBC's own unidirectional protocol S0+
The unidirectional protocol S0+ is a cost-effective
option to output the measurement data via the
S0 output. The SBC energy counter with S0 output
can output the unidirectional protocol S0+. The measurement
data is then cyclically output via the S0 output.
This functionality is integrated in the following devices:
ALD1D5FU0KAxA00:
1ph direct measuring, 230 VAC, 32 A
ALE3D5FU1KCxA00:
3ph direct measuring, 230 / 400 VAC, 65 A
AWD3D5WU0MCxA00: 3ph converter counter, 230 / 400 VAC, 5 A
Technical Data
Interfaces
Communications interfaces
RS-485 with galvanic isolation
Baud rate: 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps (autobauding)
Address switch for S-Bus address
Two rotary switches 0…9
Service interface
NFC (near field communication)
General specifications
Supply voltage
230 VAC, −20/+15%, (50 Hz)
Electrically isolated
500 VDC between power supply and RS-485 as well as between power supply and inputs
Dimensions
Housing width 2 HP (35 mm), compatible with electrical cabinet (in accordance with DIN 43880, size 2 × 55 mm)
Mounting type
DIN rail in accordance with DIN EN 60715 TH35 (1 × 35 mm)
Ambient temperature
Operation: 0…+55°C without forced ventilation / storage: −40…+70°C
Power consumption
< 4 W
This module replaces the PCD7.H108S module
Device design
3 multifunction
inputs
Temperature inputs
for PT1000 sensors
S0 pulse inputs for connect-
ing all devices to S0 pulse
output
Reading of the SBC's
own unidirectional
protocol (S0+)
S0 pulse
S0+ protocol
*
In preparation, see Chapter C2 "Product status"
RS-485
interface
Address switch
Supply
System LEDs
5 multifunction
inputs