77
saia-pcd.com
PCD
1
E-Line
Automation stations –
E-Line
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Technical Data
Interfaces
Communication interface
RS-485 with galvanic isolation
Baud rate: 9,600, 19,200, 38,400, 57,600, 115,200 bps (autobauding)
Address switch for S-Bus address
Two rotary switches 0…9
Service interface
USB (Micro-USB)
NFC (near field communication)
Additional interface
RS-485 in SASI mode for PCD1.G3601-C15
General specifications
Supply voltage
Nominal 24 VAC (50 Hz) or VDC (in accordance with EN/ IEC 61131-2)
24 VDC, –15/+20% max., incl. 5% ripple
24 VAC, −15%/+10%
Electrically isolated
500 VDC between current supply and RS-485
and between current supply and inputs/outputs
Dimensions
Housing width 6 HP (105 mm), compatible with electrical control cabinet (in accordance with DIN 43880, size 2 × 55 mm)
Mounting type
DIN rail in accordance with DIN EN 60715 TH35 (1 × 35 mm)
Ambient temperature
Operation: 0…+55°C without forced ventilation
Storage: −40…+70°C
Power consumption
Typical 2 W
Inputs and outputs
Inputs
8 digital inputs
24 VAC/VDC, 8 ms/0.2 ms input filter
4 analogue inputs
(adjustable via software)
0…10 V, ±10 V, ±20 mA (0…20 mA, 4…20 mA),
Pt/Ni1000, Ni1000TK5000 NTC, KTY
0…2,500 Ω, 0…7,500 Ω, 100 Ω…100 kΩ
12 bit resolution
Outputs
4 analogue outputs
0…10 VDC, ±10 V, 12 bit resolution
1 relay (inrush)
250 VAC/30 VDC
10 AAC (AC1)/10 ADC (resistive load)
Max. inrush current 65 A
3 relays
250 VAC/30 VDC
6 AAC (AC1)/6 ADC (resistive load)
Max. inrush current 15 A
4 Triacs
24 VAC/230 VAC, current load rating 1 A (AC)
Order details
Type
Description
PCD1.G3600-C15*
E-Line room control module
PCD1.G3601-C15*
E-Line room control module + aux. RS-485
*
In preparation, see Chapter C2 "Product status"