PP26-215 EN12a SBC System catalogue 2015/2016 - page 81

81
saia-pcd.com
PCD
1
E-Line
Automation stations –
E-Line
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Mounting and labelling in the automation control cabinet
The modules can be mounted in the standard automation control cabinet as well as
mounting in the electrical sub-distributor. Covers are available for this for easy labelling.
They also serve as contact protection for the buttons and terminals to prevent faulty
operation.
General technical data
Power supply
Supply voltage
24 VDC, −15/+20% max., incl. 5% ripple (in accordance with EN/ IEC 61131-2)
Electrically isolated
500 VDC between power supply and RS-485 and between inputs/outputs and RS-485
Power consumption max.
3 W
Interfaces
Communication
RS-485 with galvanic isolation / baud rate: 9,600, 19,200, 38,400, 57,600, 115,200 bps (autobauding)
Address switch for S-Bus
Two rotary switches 0…9
Terminating resistor
Integrated, can be activated via a wire jumper
General specifications
Ambient temperature
Operation: 0…+55°C without forced ventilation / storage: –40…+70 °C
Terminals
Push-in spring-loaded terminals – max. 1.5 mm².
Technical data for inputs and outputs
Digital inputs
Input voltage
24 VDC, high active
Relay outputs
Switching voltage max.
250 VAC/30 VDC
Switching current max.
4 A (resistive load)
Contact protection
n/a
Analogue inputs
Resolution
0…10 V: < 1.22 mV Pt1000: < 0.18 K Ni1000: < 0.12 K Ni1000TK5000: < 0.15 K 0…2,500 Ω: < 0.61 Ω
Measured values
0…10 V, Pt/Ni1000, Ni1000TK5000, NTC, KTY, 0…2,500 Ω, 100 Ω…100 kΩ can be set via FBoxes
Precision
0.3% at 25°C
Analogue outputs
Resolution
10 bits
Signal range
0…10 V (10 mA max.)
Man. Override operation
Operation via buttons and potentiometer
Digital input/output modules
Type
DI
Relays (normally open/
changeover)
AI
AO Man. override op.
Width
Power supply
PCD1.B1000-A20*
4
10 (6/4)
-
-
Yes
6 HP
24 VDC
PCD1.B1010-A20*
24
10 (6/4)
-
-
Yes
6 HP
24 VDC
PCD1.B1020-A20*
16
4 (0/4)
-
-
Yes
6 HP
24 VDC
Combined input / output modules
Type
DI
Relay (normally open / 
changeover)
AI
AO Man. override op.
Width
Power supply
PCD1.G5000-A20*
16
8 (4/4)
8
4
Yes
6 HP
24 VDC
PCD1.G5010-A20*
12
4 (0/4)
12
8
Yes
6 HP
24 VDC
PCD1.G5020-A20*
8
4 (0/4)
16
4
Yes
6 HP
24 VDC
Accessories
Description
Cover, 6 HP, holes for override operating level. For labelling the modules for mounting in automation control cabinets
*
In preparation, see Chapter C2 "Product status"
A...,71,72,73,74,75,76,77,78,79,80 82,83,84,85,86,87,88,89,90,91,...Z