139
saia-pcd.com
Consumption data collection
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Technical Data
Interfaces
Wired communication interface
RS-485 with galvanic isolation
Baud rate 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps (autobaud rate)
Wireless communication
2,400, 9,600, 38,400, 57,600 bps selectable via dial knob
Frequency band
869.475…869.6 MHz
Frequency channels (sub-bands)
4 channels selectable via dial knob
Radio range (line of sight)
Internal antenna: 1,000 m @2400 bps
External antenna: 6,000 m @2400 bps
Service interface
NFC (near field communication)
General specifications
Supply voltage
230 VAC, −20/+15%, (50 Hz)
Electrically isolated
500 VDC between power supply and RS-485
Dimensions
Housing width 2 TE (35 mm), electric control cabinet compatible (in accordance with DIN43880, dimension 2 × 55 mm)
Mounting type
on a 35-mm top-hat rail (as per DIN EN 60715 TH35)
Ambient temperature
Operation: 0…+55°C without forced ventilation
Storage: −40…+70°C
Power consumption
< 4 W
Adaptor for external antenna
An adapter is supplied with each delivery to connect an external SMA antenna to the wireless module.
The PCD1.T2000 device may be implemented in all EU countries, incl. Switzerland and Norway.
Approvals for other countries are in progress.
This module will replace the PCD7.T4850-RF module.
Accessories
PCD7.K840 External antenna
Antenna with SMA connector