133
saia-pcd.com
ref. Channel
ALD1
―
EnTotal―
Partial―
ComErr―
ref. Channel
ALE3
―En
T1―
T1part―
T2―
T2part―
Tariff―
ComErr―
ref. Channel
AWD3
―
EnTotal―
Partial―
CRatio―
ComErr―
Saia PCD®
L1
L2
L3
N
(PEN)
D /D
N
L
N
L
L1
L2
L3
N
(PEN)
Consumption data collection
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
4.4.2
Saia PCD® energy meters with SBC S-Bus interface
The energy meters with integrated S-Bus interface offer all relevant data such as energy, current, voltage, out-
put (active and reactive) and cosφ, which can be read out through the bus connection. The serial S-Bus interface
(based on RS-485) can be connected directly to the Saia PCD® range of devices. There are ready-made FBoxes
for every meter type for this connection, which are available free of charge. The S-Bus energy meters are also
available in a 2-way design (bidirectional). The bus address can be set on the display and the energy, current,
voltage and active output can be read directly.
ALD1 / AWD1
ALE3
AWD3 / AWC3
ALD1
D5FS00A2A00
ALD1
B5FS00A2A00
ALD1
D5FS00A3A00
ALD1
B5FS00A3A00
AWD1
D5WS00A2A00
ALE3
D5FS10C2A00
ALE3
B5FS00C2A00
ALE3
D5FS10C3A00
ALE3
B5FS00C3A00
AWD3
D5WS00C2A00
AWD3
B5WS00C2A00
AWD3
D5WS00C3A00
AWD3
B5WS00C3A00
AWC3
D5WS00C2A00
Tariff
1 tariff
–
–
2 tariffs
– –
–
– –
–
– – – – – –
Meter type
Unidirectional design
–
–
–
–
–
–
Bidirectional design
–
–
– –
–
–
–
–
Approvals
With MID
– –
– – –
– –
–
Without MID
– –
– –
– –
Rated/max. current
Current
I
min
= 0.01 A, I
N
= 1 A, I
max
= 1.2 A
– – – – – – – – – – – – –
I
min
= 0.05 A, I
N
= 5 A, I
max
= 6 A
– – – –
– – – –
–
I
min
= 0.25 A, I
N
= 5 A, I
max
= 32 A
– – – – – – – – – –
I
min
= 0.5 A, I
N
= 10 A, I
max
= 65 A
– – – – –
– – – – –
Measurement type
Direct measurement
–
– – – – –
Conversion up to 300 A
– – – – – – – – – – – – –
Conversion up to 500 A
– – – –
– – – – – – – – –
Conversion up to 1500 A
– – – – – – – – –
–
Operating voltage
230 VAC, 50 Hz
– – – – – – – – –
3 × 230/400 VAC, 50 Hz
– – – – –
Partial meter
Resettable
–
– –
–
–
FBoxes available for
every S-Bus meter type
SBC S-Bus
Bus system
Serial RS-485 interface
Log
S-Bus data mode
Transmission
rate
4,800, 9,600, 19,200, 38,400, 57,600,
115,200 baud. The transmission rate is
detected automatically.
Bus cable
Twisted, shielded, 2 × 0.5 mm
2
, max.1200 m
Response
time
Write: up to 60 ms
Read: up to 60 ms
Technical Data
Converter meter 3-phase
AWD3
Direct measurement 3-phase
ALE3
Converter meter
single-phase AWD1
Connection diagram for M-Bus energy meters
Direct measurement
single-phase ALD1