PP26-215 EN12a SBC System catalogue 2015/2016 - page 129

129
saia-pcd.com
S0 pulse
S0+ protocol
3 inputs
RS-485
interface
Address
switch
Supply
System
LEDs
5 inputs
Consumption data collection
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
4.3
 Saia PCD® S0 pulse counters with temperature inputs
Read and transmit S0 pulse, temperature and S0+ data
Besides the classic S0 pulses, the PCD1.H108S modules canalso capture temperatures of PT1000 sensors direct,
and read and evaluate the SBC proprietary unidirectional S0+ protocol, which is transmitted over the S0 output.
Inputs from the S0 impulse counter can be connected directly to the PT1000 temperature sensors or with the S0+
protocol. Detection of the applied medium takes place automatically. The S0 pulse counter PCD1.H108S enables
the efficient transfer, evaluation and forwarding of energy data direct to the S-Monitoring solutions of SBC without
additional complicated coupler modules.
System properties
8 Multi-functional inputs
Direct connection of PT1000 temperature sensors
Reading of S0 pulses
Reading of the unidirectional protocol S0+
Automatic integration into the S-Monitoring system
Electrical isolation between supply, bus and inputs
Pluggable terminal blocks protected by covers
Status LEDs on the front
NFC interface
Configuration and controls via FBoxes
Connection example:
Inputs:
8 Multifunction
inputs
I1 / I4 PT1000 inputs, –30…100°C, 0.5 °C precision I1-I8: S0 inputs in accordance with IEC62053−31 (S0 standard)
The inputs can also read the SBC proprietary unidirectional protocol S0+
The unidirectional protocol S0+ is a cost-effective way of
outputting the data from the S0 output. The SBC energy
meters with S0 output can display the unidirectional pro-
tocol S0+. The measurement data will then be displayed cyclically
via the S0 output.
This functionality is integrated into the following devices:
ALD1D5FU0KAxA00:
1ph direct measuring, 230 VAC, 32 A
ALE3D5FU1KCxA00:
3ph direct measuring, 230 / 400 VAC, 65 A
AWD3D5WU0MCxA00: 3ph converter meter, 230 / 400 VAC, 5 A
Technical Data
Interfaces
Communications interfaces
RS-485 with galvanic isolation
Baud rate: 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps (autobaud rate)
Address switch for S-Bus address
2 rotary switches 0…9
Service interface
NFC (near field communication)
General specifications
Supply voltage
230 VAC, −20/+15%, (50 Hz)
Electrically isolated
500 VDC between power supply and RS-485 as well as between power supply and inputs
Dimensions
Housing width 2 TE (35 mm), electric control cabinet compatible (in accordance with DIN43880, dimension 2 × 55 mm)
Mounting type
Top-hat rail as per DIN EN 60715 TH35 (1 x 35 mm)
Ambient temperature
Operation: 0…+55°C without forced ventilation Storage: −40…+70°C
Power consumption
< 4 W
This module will replace the PCD7.H108S module
Device installation
Temperature inputs
for PT1000 sensors
S0 pulse inputs to connect
all devices with S0 pulse
output
Reading of the SBC pro-
prietary unidirectional
protocol (S0+)
A...,119,120,121,122,123,124,125,126,127,128 130,131,132,133,134,135,136,137,138,139,...Z