PP26-215 EN12a SBC System catalogue 2015/2016 - page 149

149
saia-pcd.com
Switch cabinet components
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
5.1 
SBC Power: Power units with 24 VDC output
SBC power units provide an ideal power supply for automation solutions owing to their high level of resistance to interference.
They can also be used to operate high-output loads, as they can be heavily overloaded for short periods. The full extent of their
flexibility is demonstrated by the option to connect multiple devices in parallel to increase the maximum output current or to
connect them in series to achieve different voltage levels.
Power unit overview
SBC Power Flex single-phase 110/230 VAC
Q.PS-AD2-2402F (up to 3 A)
Q.PS-AD2-2405F (up to 7.5 A)
Q.PS-AD2-2410F (up to 14 A)
SBC Power Flex single-phase or double-phase 230/400 VAC
Q.PS-AD3-2405F (up to 7.5 A)
Uninterruptible power unit single-phase 110/230 VAC with
intelligent battery charger
Q.PS-ADB-2405-1 (5 A)
SBC CC single-phase 28 VAC/40 VDC
Q.PS-AD1-2403 (3 A)
Q.PS-AD1-2405 (5 A)
System properties in general
Short-circuit protection
Overload protection
IP 20 housing for mounting on DIN rail
Properties of Flex types 24xxF
Power boost: +40% additional output current up to 60 °C
for at least 3 minutes
With AD2/3-2405F and 2410F, a range of short-circuit
modes available
“Power good” relay for status display
With 2410F, simple parallel connection (via jumper)
to increase max. output current
Output voltage up to 150 VDC possible in serial mode
Extremely compact
AD3-2405F can be used as either a single-phase
or double-phase power unit
Properties of the uninterruptible power
unit
3-stage automatic charging curve to compensate
the self-discharge of the battery
Automatic real-time diagnostics of the battery status
and test function for the battery service life
Any battery fault can be easily identified via blinking
codes of the diagnostics LED
Option of status and battery fault reporting in the control
system via 2 potential-free contacts
Adjustable charging current 1…5 A
Standards and certifications
In accordance with EMC 2004/108/EEC Electromagnetic
Compatibility - 2006/95/EEC Low voltage - cULus Listed 508
Industrial Control Equipment
Electrical safety:
For the assembly devices in accordance with IEC/EN 60950
(VDE 0805) and EN 50178 (VDE0160). The unit must be installed
in accordance with IEC/EN 60950.
EMC Generic
Immunity in accordance with EN 61000-6-2
Noise emission in accordance with EN 61000-6-4
From left to right: Q.PS-ADB, Q.PS-AD2, Q.PS-AD1
Dimensions
Q.PS-AD2-2402F
Q.PS-AD2-2405F
Q.PS-AD2-2410F
Q.PS-AD3-2405F
Q.PS-ADB-2405-1
Q.PS-AD1-2403
Q.PS-AD1-2405
Width (W)
50 mm 55 mm 72 mm 55 mm 65 mm 50 mm 50 mm
Height (H)
120 mm 110 mm 115 mm 110 mm 115 mm 95 mm 95 mm
Depth (D)
50 mm 105 mm 135 mm 105 mm 135 mm 61 mm 61 mm
Weight
0.3 kg
0.6 kg
0.6 kg
0.6 kg
0.6 kg
0.2 kg
0.2 kg
W
D
H
A...,139,140,141,142,143,144,145,146,147,148 150,151,152,153,154,155,156,157,158,159,...Z