PP26-215 EN12a SBC System catalogue 2015/2016 - page 146

146
saia-pcd.com
SBC
Consumption data collection
Onboard inputs/outputs
Inputs:
6 Digital inputs (4 + 2 interrupts)
15…30 VDC, 8 ms / 0.2 ms input filter
Terminal X1
2 Analogue inputs, selectable via DIP switch,
preconfigured for Ni1000 in the default setup
–10…+10 VDC, 0…±20 mA, Pt1000, Ni1000, Ni1000 L&S,
0…2.5 kΩ, 12 bit resolution
Terminal X1
Outputs:
4 digital outputs
24 VDC / 0.5 A
Terminal X0
1 PWM output
24 VDC / 0.2 A
Terminal X0
selectable/configurable via PG5
4 Digital inputs or outputs,
preconfigured for digital inputs in the default setup
24 VDC/data such as digital inputs or digital outputs
Terminal X0
1 Watchdog relay or as a make contact
48 VAC or VDC, 1 A mount a freewheeling diode over the load when
switching DC tension
Terminal X3
General specifications
Operating voltage
24 VDC, –20/+25% max. incl. 5% ripple (as defined by EN/IEC 61131-2)
Battery for data backup (replaceable)
Lithium battery with a service life of 1 to 3 years
Operating temperature:
0…55 °C
Dimensions (W x H × D)
142 × 142 × 60 mm
Mounting type
Top-hat rail in accordance with DIN EN 60715 TH35 (1 x 35 mm) or on a level surface
Protection type
IP 20
Capacity 5 V/+V (24 V) internal
max. 500 mA/200 mA
Power consumption
typically 12 W
Automation server
Flash memory, file system, FTP and web server, email, SNMP
Installation notes and recommendations
Assembly in the distribution board
The Saia PCD1.M0160E0 has the dimensions 142 x 142 × 60 mm excluding terminals and connections.
For easy assembly, a gap of 55 mm above the DIN rail and 75 mm below it is recommended.
Ethernet cable
For installation in the sub-distributor, an angled or flexible network cable (e.g. SlimWire PRO) is recommended.
The installation of a conventional network cable cannot guarantee the assembly of the sub-distributor cover.
Technical Data
PCD1.M0160E0
Memory and file system
Program memory, DB/text (Flash)
1 Mbyte
User memory, DB/text (RAM)
1 Mbyte
User flash file system onboard
128 Mbyte
Integrated communication
Ethernet connection (2-port switch)
 10/100 Mbit/s, full-duplex, auto-sensing, auto-crossing
Yes
USB connection
USB 1.1 device, 12 Mbit/s
Yes
RS-485 (terminal X3), up to 115 kbit/s
Yes
Overview of Saia PCD® e-Controller
Automation server
integrated
into base unit
For interface options and accessories, see Section 1 "Automation stations – PCD1"
A...,136,137,138,139,140,141,142,143,144,145 147,148,149,150,151,152,153,154,155,156,...Z