PCD1.G360x-C15
-
E-Line room control module
-
PCD1.G3600-C15:
E-Line input/output module for room automation
freely programmable
Supply 24 VAC/VDC
8 digital inputs 24 VAC/VDC
3 relay changeover 230 VAC / 30 VDC, 6 A, max. inrush current 15 A
1 relay changeover 230 VAC / 30 VDC, 10 A, max. inrush current 65 A
4 Triacs 24 VCA or 230 VAC/1 A
4 analog inputs 12 bits, 0...10 V, ±10 V,
0(4)...20 mA, Pt/Ni 1000, NTC,
0...2500 Ohm, 0...7500 Ohm, 0...300 kOhm
4 analog outputs 12 bit, 0...10 V (3 mA max.)
3 interfaces: RS-485 (S-Bus), USB & NFC (Service)
PCD1.G3601-C15:
With auxiliary RS-485 interface
-
PCD1.G1100-C15
-
E-Line light & blind module
-
E-Line input/output module for light & blind
freely programmable
Supply 24 VAC/VDC
4 digital inputs 24 VAC/VDC
2 relay change over 230 VAC / 30 VDC, 8 A, max. inrush current 15 A, incl. galvanically isolated current measurement
2 analog outputs 12 bits, 0...10 V (3 mA max.)
3 interfaces: RS-485 (S-Bus), USB & NFC (Service)
Documentation
System Catalogue : E-Line
Extract | 26-215_A0160 | System Catalogue : E-Line |
System Catalogue : Room Automation
Extract | 26-215_B0400 | System Catalogue : Room Automation |
Room automation is a crucial component for room comfort and also reduces operating costs to efficient levels. Energy efficiency therefore plays a vital role along with a comfortable interior temperature and the intuitive operation of the various room functions.
This can be achieved by room automation from SBC.
ENG18 |
![]() |
2.44 MB | Download | ||
FRA18 |
![]() |
2.45 MB | Download | ||
GER18 |
![]() |
2.45 MB | Download | ||
ITA18 |
![]() |
2.43 MB | Download |
E-Line-Room-Control
Flyer | PP31-026 | E-Line-Room-Control |
PCD1.G360x-C15 E-Line room control module
Datasheet | PP31-110 | PCD1.G360x-C15 E-Line room control module |
PCD1.G1100-C15 E-Line Licht & Beschattungsmodul
Datasheet | 31-111 | PCD1.G1100-C15 E-Line Licht & Beschattungsmodul |
E-Line Programmable Quick Start
Minimal Firmware configuration
The minimum Firmware for the head station is 1.24.XX
Firmware used in production
Firmware used in production PCD1.E-Line programmable modules and RIO I/O modules
Firmware Package | 1.04.24/1.08.06/1.08.13 | Firmware used in production PCD1.E-Line programmable modules and RIO I/O modules |
This firmware is used in the PCD production and the PCD1 E-Line programmable modules and RIO I/O modules L-Series and S-Seires are shipped with this firmware.
The programmable I/O modules:
FW 1.04.24
PCD1.G1100-C15
PCD1.G360x-C15
PCD1.F2611-C15
PCD1.W5300-C15
The RIO modules L-Series:
FW 1.08.06
PCD1.B1000-A20
PCD1.B1010-A20
PCD1.B1020-A20
PCD1.G5000-A20
PCD1.G5010-A20
PCD1.G5020-A20
The RIO modules S-Series:
FW 1.08.13
PCD1.A1000-A20
PCD1.A2000-A20
PCD1.B5000-A20
PCD1.B5010-A20
PCD1.E1000-A20
PCD1.G2000-A20
PCD1.G2100-A20
PCD1.G2200-A20
PCD1.W5200-A20
1.04.24/1.08.06/1.08.13 |
![]() |
.zip | 0.57 MB | Download |
Good to know
PG5 2.1.410 or later is to be used for working with the PCD1 E-Line
Good to know

The differences between firmware version 1.04.07 and 1.04.24 are listed in FAQ 101990
PCD1 / E-Line
- New firmware 1.08.16 for PCD1 E-Line Rio's (FAQ #102061)
- Is it possible to know the firmware version of the Top Print of the PCD1 E-Line RIOs? (FAQ #102059)
- What are the differences between the COSinus firmwares FW 1.28.11 and FW 1.28.51? (FAQ #102058)
- Why the RS-485 S-Bus communication between the PCD master and the slave does fail sometime, if FW 1.28.20…1.28.33 is used? (FAQ #102026)
- What are the differences between the COSinus firmwares FW 1.28.11 and FW 1.28.51? (FAQ #102010)
- PG5 2.1 and 2.2 with E-Line S-Bus communication library < 1.2.110, why the S-Bus communication on the master PCD stops either after a certain time? (FAQ #102009)
- PG5 2.1 and PG5 2.2 with S-Bus communication library 2.7.370, why the S-Bus communication on the master PCD stops either after a certain time or after the download of the program? (FAQ #102008)
- No Refresh from State of I/O's from E-Line Rio- Moduls after Fbox Update (FAQ #102001)
- What is the meaning of E-Line RIO – Leds & status specifications (FAQ #101998)
- What are the differences between E-Line firmwares FW 1.04.07 and 1.08.06? (FAQ #101990)