PP26-215 EN12a SBC System catalogue 2015/2016 - page 67

67
saia-pcd.com
PCD
1
SNMP
Automation stations – Saia PCD1
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Onboard inputs/outputs
Inputs:
6 Digital inputs (4 + 2 interrupts)
15…30 VDC, 3 ms / 0.2 ms input filter
Terminal X1
2
Analogue inputs, selectable via DIP switch, preconfigured for Ni1000 in
the default setup
–10…+10 VDC, 0…±20 mA,
Pt1000, Ni1000, Ni1000 L&S, 0…2.5 kΩ, 12 bit resolution
Terminal X1
Outputs:
4 Digital outputs
24 VDC / 0.5 A
Terminal X0
1 PWM output
24 VDC / 0.2 A
Terminal X0
selectable/configurable via PG5
4 Digital inputs or outputs,
preconfigured for digital inputs in the
default setup
24 VDC / data such as digital inputs or Digital outputs
Terminal X0
1 Watchdog relay or as make contact
48 VAC or VDC, 1 A
with DC switching voltage a free-wheeling diode should be connec-
ted in parallel to the load
Terminal X3
General specifications
Operating voltage
24 VDC, –20/+25% max. inkl. 5% ripple (in accordance with EN/IEC 61131-2)
Battery for data backup (replaceable)
Lithium battery with a service life of 1 to 3 years
Operating temperature:
0…55 °C
Dimensions (W × H × D)
142 × 142 × 61 mm
Mounting location
DIN rail in accordance with DIN EN 60715 TH35 (1 × 35 mm) or on a level
surface
Protection type
IP 20
Capacity 5 V/+V (24 V) internal
max. 500 mA/200 mA
Power consumption
typically 12 W
Automation Server
Flash memory, file system, FTP and web server, email, SNMP
Installation notes and recommendations
Assembly in the electrical distribution unit
The Saia PCD1.M0160E0 has the dimensions 142 × 142 × 61 mm excluding terminals and connections.
For easy assembly, a gap of 55 mm above the DIN rail and 75 mm below it is recommended.
Ethernet cable
For installation in the sub-distributor, an angled or flexible network cable (e.g. SlimWire PRO) is recommended.
With installation of a conventional network cable, assembly of the sub-distributor cover cannot be guaranteed.
Technical data
PCD1.M0160E0
Memory and file system
Program memory, DB/text (Flash)
1 MB
User memory, DB/Text (RAM)
1 MB
Onboard flash file system
128 MB
Integrated communication
Ethernet connection (2-port switch)
10/100 Mbit/s, full-duplex, auto-sensing, auto-crossing
Yes
USB port
USB 1.1 device 12 Mbit/s
Yes
RS-485 (terminal X3)
up to 115 kbit/s
Yes
Overview Saia PCD® E-Controller (PCD1.M0160E0)
Automation Server
Integrated
into the base unit
Analogue output module Saia PCD7.W600
This module has 4 analogue outputs 0 to +10 V with a 12-bit resolution and has been specifically developed to
use with the new PCD1 CPUs (PCD1.M2xxx, PCD1.M0160E0, PCD1.M2110R1). It can be plugged into slot A of the
PCD1 CPU like the PCD7.F1xxS communication module.