PP26-215 EN12a SBC System catalogue 2015/2016 - page 62

62
saia-pcd.com
PCD
1
142
49
226
Automation stations – Saia PCD1
1.4.2
Saia PCD1.Room (PCD1.M2110R1)
Saia PCD1.Room (PCD1.M2110R1) is a programmable room controller for complex solutions with many commu-
nication options. In addition to the I/Os that are already integrated, the controller has a free I/O slot for individual
expansion with inputs/outputs or communication options. Web/IT functions for mobile operation, for instance,
are also already onboard. Furthermore, Saia PCD1.Room offers various possibilities for integrating other systems
in the room using standard communication interfaces. (Energy) efficient and individual room automation can be
easily implemented as a result. The controller also provides a good basis for achieving the energy efficiency classes
in accordance with EN 15232:2012.
Lighting, sun protection and individual room regulation can be optimally coordinated with one another with this controller. This example showing possible assignments
was compiled based on applications in accordance with the VDI 3813 list of room automation functions and the DIN EN 15232 list of building automation functions.
1×serial communication
RS-485: e.g. connec-
tion external receiver
EnOcean
1× make contact 48VAC
e.g. switching contact
Power supply 24VDC
USB port
Ethernet connection
(2-port switch) e.g. to the Inter-
net (remote control via browser
is possible as a result)
1×optional terminals for
serial communication
depending on the PCD7.
F1xxS module
e.g.
– MP-Bus (with PCD7.
F180S) for Belimo
actuating drives.
2× analogue inputs:
– 10…+10VDC, 0…+/–20 mA,
Pt1000, Ni1000, Ni1000 L&S,
0…2.5 kΩ
e.g.
– Brightness measurement
– Air temperature measurement
6× digital inputs:
15…30VDC
e.g.
– Presence detection
–Window monitoring
4× Digital inputs/outputs
(selectable)
24VDC
e.g.
– Dewpoint monitoring
–Time switch program
5× digital outputs: 24VDC
e.g.
– Signal presence
– Switch/set binary output
2× analogue outputs: 0…10
VDC, 0(4)…20 mA
e.g.
–Volume flow control
– Adjust temperature
setpoint
4× analogue inputs: 0…10VDC,
0(4)…20 mA Pt500, Pt1000,
Ni1000
e.g.
– Air quality measurement
– Precipitation detection
Expansion options I/O or com-
munication module e.g. DALI
(PCD2.F2610)
Device design with connection example
The Smart RIO Manager function is not supported!
Mounting
Dimensions
Power supply and connection concept
Further information is provided in the Chapter Saia PCD3
power supply and connection concept, and in the Manual
26-875.
on two DIN rails
(2 × 35 mm in accordance
with DIN EN 60715 TH35)
on a level surface
Supply
Groundbar
1.5mm
2
 /max.25cm
Compact mass:
142 × 236 × 49 mm