PP26-215 EN12a SBC System catalogue 2015/2016 - page 60

60
saia-pcd.com
PCD
1
M1
SlotA
X2
X1
X0
X3
PCD7.R55xM04
PCD7.R610
Automation stations – Saia PCD1
Communication
Electrical
isolation
Internal current con-
sumption 5V +V (24 V) Slot
I/O
connector
type
1)
PCD7.F110S
RS-485/RS-422
---
40 mA
Slot A
PCD7.F121S
RS-232 with RTC/CTS, DTR/DSR, DCD
suitable for modem, EIB connection
---
15 mA
Slot A
PCD7.F150S
RS-485 with termination resistors that can be activated
130 mA
Slot A
PCD7.F180S
Belimo MP-Bus, for connecting up to 8 drives on one line
---
15 mA 15 mA Slot A
PCD2.F2100
RS-422/RS-485 plus PCD7.F1xxS as option
---
110 mA
IO 0/1
2× K
PCD2.F2150
BACnet® MS/TP RS-485 plus PCD7.F1xxS as an option
---
110 mA
IO 0/1
2× K
PCD2.F2210
RS-232 plus PCD7.F1xxS as an option
---
90 Ma
IO 0/1
2× K
PCD2.F2400
L
on
W
orks
® interface module
---
90 Ma
IO 0/1 L9
PCD2.F2610
DALI Master for up to 64 DALI devices
---
90 Ma
IO 0/1 L
PCD2.F27x0
M-Bus master with 2 M-Bus interfaces
---
70 mA
8 mA IO 0/1 L
PCD2.F2810
Belimo MP-Bus plus PCD7.F1xxS as an option
---
90 Ma
15 mA IO 0/1
2× K
1)
Plug-in I/O terminal blocks are included with I/O modules.  Spare terminals, ribbon connectors with system cables and separate terminals are
ordered as accessories.
In addition to the onboard interfaces, the interface functions can also be expanded in a modular
way using the various slots. Numerous protocols are therefore supported by the Saia PCD1.M2 series.
Detailed information and an overview is contained in the Chapter BA communication systems.
Saia PCD1.M2xxx interface options
System properties of PCD2.F2xxx modules
The following points must be noted when using the PCD2.F2xxx interface modules:
Max. 2 modules PCD2.F2xxx (4 interfaces) can be used in slots I/O 0/1 per PCD1.M2 system.
Consult the information and examples provided in the Manual 26/875 for PCD1.M2 to determine
the maximum communication capacity for each PCD1.M2 system.
Memory expansion and communication
PCD7.R550M04
Flash memory module with a 4 MB file system (for user program backup, web pages, etc.)
M1
PCD7.R560
Flash memory module for BACnet® firmware
M1
PCD7.R562
Flash memory module for BACnet® firmware with 128 MB file system
M1
PCD7.R580
Flash memory module for L
on
IP firmware
M1
PCD7.R582
Flash memory module for L
on
IP firmware with 128 MB file system
M1
PCD7.R610
Basic module for Micro SD flash card
M1
PCD7.R-MSD1024
Micro SD flash card 1024 MB, PCD formatted
PCD7.R610
The onboard memory of the Saia PCD1.M2xxx can be expanded using a Saia PCD7.Rxxx module in slot M1.
In addition, the Saia PCD1.M21x0 can be expanded with BACnet® IP or L
on
IP.
Additional information about the memory management and structure is contained in the Chapter Saia PCD® System
Description.
The use of external modem modules such as Q.M716-KS1 is recommended.
The PCD2.T8xx modem modules can only be used with a PCD7.F121S module.
External wiring is therefore required.
Memory modules
IO0
IO1
A...,50,51,52,53,54,55,56,57,58,59 61,62,63,64,65,66,67,68,69,70,...Z
Powered by FlippingBook