PP26-215 EN12a SBC System catalogue 2015/2016 - page 64

64
saia-pcd.com
PCD
1
W
module
M1
SlotA
X2
X1
X0
X3
PCD7.R55xM04
PCD7.R610
Automation stations – Saia PCD1
In addition to the onboard interfaces, the interface functions can also be expanded in a modular
way using the various slots. Numerous protocols are therefore supported by the Saia PCD1.M2110R1.
A detailed list of all the protocols can be found in the Chapter BA communication systems.
Saia PCD1.Room (PCD1.M2110R1) interface options
System properties of PCD2.F2xxx modules
The following points must be noted when using the PCD2.F2xxx interface modules:
Per PCD1.M2110R1 Room Edition a max. of 1 module PCD2.F2xxx (2 interfaces) can be used with slot I/O0.
Consult the information and examples provided in the Manual 27/619 for PCD1.M2110R1 to determine the maximum
communication capacity for each PCD1.M2 system.
The onboard memory can be expanded using a PCD7.Rxxx module in slot M1. In addition, BACnet® IP or L
on
IP can be
activated.
Additional information about the memory management and structure is contained in the Chapter Saia PCD® System
description.
Memory modules
IO0
Memory expansion and communication
PCD7.R550M04
Flash memory module with a 4 MB file system (for user program backup, web pages, etc.)
M1
PCD7.R560
Flash memory module for BACnet® firmware,
M1
PCD7.R562
Flash memory module for BACnet® firmware with 128 MB file system
M1
PCD7.R580
Flash memory module for L
on
IP firmware
M1
PCD7.R582
Flash memory module for L
on
IP firmware with 128 MB file system
M1
PCD7.R610
Basic module for Micro SD flash card
M1
PCD7.R-MSD1024
Micro SD flash card 1024 MB, PCD formatted
PCD7.R610
Communication
Electrical
isolation
Internal current con-
sumption 5V +V (24 V) Slot
I/O
connector
type
1)
PCD7.F110S
RS-485/RS-422 not electrically isolated
---
40 mA
Slot A
PCD7.F121S
RS-232 with RTC/CTS, DTR/DSR, DCD suitable for modem or EIB
connection
---
15 mA
Slot A
PCD7.F150S
RS-485 electrically isolated, with termination resistors that can
be activated
130 mA
Slot A
PCD7.F180S
Belimo MP-Bus, for connecting up to 8 drives on one line
---
15 mA 15 mA Slot A
PCD2.F2100
RS-422/RS-485 (not electrically isolated) plus PCD7.F1xxS
as an option
---
110 mA
IO 0/1
2× K
PCD2.F2150
BACnet® MS/TP RS-485 plus PCD7.F1xxS as an option
---
110 mA
IO 0/1
2× K
PCD2.F2210
RS-232 plus PCD7.F1xxS as an option
---
90 Ma
IO 0/1
2× K
PCD2.F2400
L
on
W
orks
® interface module
---
90 Ma
IO 0/1 L9
PCD2.F2610
DALI master for up to 64 DALI devices
---
90 Ma
IO 0/1 L
PCD2.F27x0
M-Bus master with 2 M-Bus interfaces
---
70 mA 8 mA IO 0/1 L
PCD2.F2810
Belimo MP-Bus plus PCD7.F1xxS as an option
---
90 Ma
15 mA IO 0/1
2× K
1)
Plug-in I/O terminal blocks are supplied with I/O modules.
Spare terminals, ribbon connectors with system cables and separate terminals are ordered as accessories.