128
saia-pcd.com
SBC
kWh
kWh
58
85
45
35
28
43
1)
Consumption data collection
4.2
Saia PCD® S0 impulse counter
S0 Collect, convert and transmit pulses
If already installed meters, which are not bus-capable, are to be integrated into an automation system, the Saia PCD7.H104 S0 pulse
counter is the easiest way. This is the case for refurbishments, for example, if the existing meter infrastructure has to be made bus-capable
and there is no question of buying new meters. With this S0 pulse counter, meters (electricity, water, heat, etc.) with an S
0
pulse output
from any manufacturer can be connected directly using a serial RS-485 S-Bus or Modbus connection to the Saia PCD, the e-Monitor or
any controller. This enables efficient transfer, evaluation and forwarding of energy data without additional complicated coupler modules.
For connection to Saia PCD® systems, there are ready-made FBoxes. Via the interfaces, the number or valence of pulses can be trans-
mitted.
1)
Chapter 4.7 "e-Monitor" contains more information ON THIS TOPIC
FBoxes for integration into FUPLA
General technical data
Operating voltage
230 VAC (–20/+15 %)
Current draw
<12 mA
Power consumption
<3 W
Number of S0 inputs
4, in accordance with S0 IEC62053-31
Frequency
max. 17 Hz
Pulse low/high
Min. 30 ms
S-Bus version
Order number
PCD7.H104SE
Log
S-Bus data mode
Bus system
Serial RS-485 interface
Transmission rate
2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200
The transmission rate is detected automatically
Bus length (max.)
1,200 m (without amplifier)
Response time
Write: 30 ms
System response time
Read: 20 ms
Modbus version
Order number
PCD7.H104D
Log
Modbus RTU as per IDA specification
Bus system
Serial RS-485 interface
Transmission rate
(bit/s)
2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200
The transmission rate is detected automatically
Bit settings
8 databit, even parity, 1 stop bit
8 databit, odd parity, 1 stop bit
8 databit, no parity, 2 stop bit
Maximum bus length
1,200 m (without amplifier)
Response time
Type 5 characters
System response time
max. 60 ms
S0 pulses
S0 pulses
Size
Device PCD7.H104DZ44 must be used for parity 8N1!