PP26-215 EN11 System catalogue 2014/2015 - page 136

136
saia-pcd.com
Cabinet components
SBC Power: Technical data
Overload protection
Input data
Q.PS-AD2-2402F
Q.PS-AD2-2405F
Q.PS-AD2-2410F
Input voltage
115…230 VAC
Permitted voltage range:
90…264 VAC
90…135 / 180…264 VAC
Inrush current (at V
n
and I
n
)
≤ 7 A ≤ 5 ms
≤ 11 A ≤ 5 ms
≤ 16 A ≤ 5 ms
Input frequency
47…63 Hz (±6%)
Input current (at operating voltage)
1.0…0.7 A
2.8…1.0 A
3.3…2.2 A
Internal fuse
4 A
6.3 A
External fuse recommended
Fast-acting 6 A
Fast-acting 10 A
Fast-acting 14 A
Output data
Output voltage (V
n
) / nominal current (I
n
)
24 VDC ±3% / 2.5 A
24 VDC ±3% / 5 A
24 VDC ±3% / 10 A
Adjustment range (V
adj
)
22…27 VDC
Switch-on delay
2 s (max.)
1 s (max.)
Start-up with capacitive load
≤ 50000 μF
Continuous running at ≤40 °C
3 A (230 VAC)/2 A (115 VAC)
7.5 A
14 A
Continuous running at ≤50 °C
2.5 A (230 VAC)/1.5 A (115 VAC)
6.0 A
12 A
Continuous running at ≤60 °C
---
5.0 A
10 A
Maximum continuous current
---
---
---
Reserve out current (within 3 minutes at ≤60 °C)
3.5 A
7.5 A
14 A
Short-circuit current (I
cc
)
7 A
16 A
30 A
Residual ripple
≤ 80 mVpp
Efficiency (at 50% in)
≥ 88%
≥ 91%
Short-circuit protection
Yes
Yes + 3 modes
Overload protection
Yes
Overvoltage output protection
Yes (max. 35 VDC)
Parallel connection
Yes
Yes – simple
Signal output (floating switch contacts)
Switching capacity
---
1 A / 30 VDC
Voltage drop >10%
---
Yes
Climatic data
Ambient temperature (operation)
–25…+70 °C
Derating >50 °C, 2.5%/°C)
–25…+70 °C
Derating >60 °C, 2.5%/°C)
Ambient temperature (storage)
–40… +85 °C
Humidity, no moisture condensation
95% at +25 °C
Mode
Jumper Characteristic
Hiccup mode
Automatic restart
(default setting)
Attempts to switch
on the output volt-
age again every 2
seconds.
HICCUP
MODE
24
16
8
4
0 2
6 8 10 12
20
4
12
28
Icc
In × 1.5
In (60 °C)
4
0 2
6 8 10 12
Output Voltage [V]
Load [A]
Time [sec]
Time [sec]
I
overload
Manual reset
mode
For a restart, it is nec-
essary to switch off
the input voltage for
approx. 1 minute.
MANUAL
RESET
24
16
8
4
0 2
6 8 10 12
20
4
12
28
Icc
In × 1.5
In (60 °C)
4
0 2
6 8 10 12
1 Min.
Output Voltage [V]
Load [A]
Timet [sec]
Time [sec]
Mode
Jumper Characteristic
Continuous out
mode
The output current
remains at a high
value and the output
voltage is almost
0 volts.
CONTINUOUS
OUT MODE
24
16
8
4
0 2
6 8 10 12
20
4
12
28
Icc
In × 1.5
In (60 °C)
4
0 2
6 8 10 12
Output Voltage [V]
Load [A]
Time [sec]
Time [sec]
I
overload
A...,126,127,128,129,130,131,132,133,134,135 137,138,139,140,141,142,143,144,III,IV,...Z