PP26-215 EN11 System catalogue 2014/2015 - page 126

126
saia-pcd.com
SBC
S-Monitoring
The S-Monitoring COSinus function comprises the following three parts:
1. Autoscan of S-Bus energy meters and pulse counters
If the S-Bus Autoscan is activated, meters connected to the RS-485 interface are automatically detected and read.
By permanently requesting the meter data, remote diagnosis of the S-Bus meters and bus connection is possible.
S-Monitoring COSinus function
S-Monitoring is an integral part of the COSinus operating system and is integrated in all Saia PCD® controllers ending with
xx60 and having the pWeb-Panel MB. It is activated in the PG5 Device Configurator and automatically scans connected
meters. The data is saved on the file system. In addition to connected S-Bus meters, any meter values available in the pro-
gram can also be integrated.
The S-Monitoring function can read three different types of meters:
f
Connected S-Bus energy meters and pulse counters (PCD7.H104SE)
f
Other incremental meter values
(M-Bus, Modbus, etc. are referred to as “custom counters” and captured via FBoxes in the Fupla program)
f
Groups of meters
Excel Report Tool
When the COSinus function is activated,
the data can simply be imported into
Excel without programming.
Download:
4.5
Basic functions of the S-Monitoring application
Function for automatic capturing and saving of energy meter values –
integrated in the operating system of the Saia PCD®
The S-Monitoring application works on all controllers ending in xx60 and on the pWeb Panels.
The application consists of a COSinus function and an associatedWeb Editor project.
This makes it possible to capture, save and visualise data without significant programming effort.
With S-Bus meters, this works without any program in the controller.
3. Saving the meter values in CSV files
The values of the energy meters connected are saved once a day at midnight in a CSV file on the internal file system of the
PCD. The daily, weekly and monthly consumption can be calculated from this data. If an additional memory card is inserted,
the values can be saved at 5-60 minute intervals. This makes it possible to visualise consumption over a day.
2. Provision of meter values via NT-EM tags (CGI interface)
All data and basic functions can be called via CGI tags. These functions can therefore be accessed via the web interface or
by other programs (e.g. Excel). The controller does not need a Fupla or IL program (see document 27/623).
NT-EM tag (CGI command) in the web browser:
‹
Command
‹
Value
A...,116,117,118,119,120,121,122,123,124,125 127,128,129,130,131,132,133,134,135,136,...Z