saia-pcd.com
105
PCD
7L
2
HMI Visualization
and operating
1
Automation
stations
5
4
Cabinet
components
Consumption data
acquisition
3
Dedicated
room controller
Dedicated room controller
Product overview: S-Bus and L
on
W
orks
®
room controller
S-Bus
L
on
W
orks
System catalogue
PCD7 product line
Supply voltage
230 VAC
+10%/–15%
230 VAC
+10%/–15%
24 VAC
+10%/–10%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
Inputs
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Digital inputs
1× window
contact and
1× multi-
functional
1× window
contact and
1× multi-
functional
1× window
contact and
1× multi-
functional
1× window
contact and
1× multi-
functional
4× multi-
functional
1× window
contact and
1× multi-
functional
4× multi-
functional
4× multi-
functional
4× multi-
functional
Operating state response
Yes
Yes
Yes
Yes
Yes
Yes
Yes
---
Yes
Analogue inputs 0…10 VDC
---
1×
0…10 VDC
1×
0…10 VDC
1×
0…10 VDC
---
---
1×
0…10 VDC
2×
0…10 VDC
1×
0…10 VDC
Temperature sensor
1× NTC
10 kOhm
1× NTC
10 kOhm
1× NTC
10 kOhm
1× NTC
10 kOhm
1× NTC
10 kOhm
1× NTC
10 kOhm
1× NTC
10 kOhm
2× NTC
10 kOhm
1× NTC
10 kOhm
Setpoint value adjuster
(10 kOhm potentiometer)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
---
Yes
Outputs
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Digital outputs TRIAC
2× 230 VAC
(total max.
800 mA)
2× 230 VAC
(total max.
800 mA)
2× 24 VAC
(total max.
800 mA)
2× 24 VAC
1)
2× 230 VAC
(total max.
800 mA)
2× 230 VAC
(total max.
800 mA)
2× 24 VAC
1)
4× 230 VAC
(total 2
×
max. 800 mA)
2× 230 VAC
(total max.
800 mA)
Relay outputs 3-level
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
---
1× 230 VAC
(3 A)
Relay outputs 1-level
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
2× 230 VAC
(10 A)
1× 230 VAC
(10 A)
Analogue outputs (total max. 2 mA)
---
2×
0…10 VDC
2×
0…10 VDC
2×
0…10 VDC
---
2×
0…10 VDC
2×
0…10 VDC
2×
0…10 VDC
2×
0…10 VDC
Analogue outputs
with additional 24 VAC power supply
---
---
Yes
Yes
1)
---
---
Yes
1)
---
—
Extension modules
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Light modules
Yes
Yes
Yes
Yes
---
Yes
4)
---
Yes
2)
---
Shade modules
Yes
Yes
Yes
Yes
---
Yes
3)
---
---
---
Possible applications
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Electrical heating only
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 pipes for heating or «Change over»
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 pipes for cooling or «Change over» with
electrical heating
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4 pipes for heating and cooling
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4 pipes for heating and cooling and
electrical heating (secondary)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4 pipes for heating and cooling and
electrical heating (primary)
---
---
---
---
Yes
Yes
Yes
Yes
Yes
2 × 2 pipes for heating, cooling or
changeover
Yes
Yes
Yes
Yes
---
---
---
---
---
RIO
Yes
Yes
Yes
Yes
---
---
---
---
---
Direct control of outputs
---
---
---
---
Yes
---
Yes
---
Yes
Special functions
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Air quality control (CO
2
)
Yes
Yes
Yes
Yes
---
---
Yes
---
Yes
Master / Slave
Yes
Yes
Yes
Yes
---
---
---
---
---
Application examples:
Fan coil, chilled beam, air quality control (combined with heating and second level cooling
(radiator/cooling ceiling-, underfloor heating/cooling ceiling combination, changeover operation (e.g. for cooing/heating ceiling), VAV
1)
PCD7.L6x4-1: The total power consumption of valves must be max. 7 W. Output voltage : 24 VAC; -15 %/+35 %
2)
Without automatic function
3)
Without blind slats rotation
4)
Without dimming
Controlled valves and required I/O
Thermal valve:
1 digital output (Triac PWM)
0…10 V valve:
1 analogue output (0…10 VDC)
3-point valve:
2 digital outputs (Triac PWM)
6-way valve:
1 analogue output (0…10 VDC)
can only be connected to one 6-way valve
Controlled motors and required I/O
VAV controller:
1 analogue output (0…10 VDC)
3-level fan:
1 relay output 3-level
Fan with variable rpm:
1 analogue output (0…10 VDC)
with PCD7.L601-1…L604-1 and
PCD7.L614…L616 devices only
Electric heating:
1 relay output 1-level
*
In preparation, see chapter C2 «Product status»