saia-pcd.com
117
PCD
7L
Dedicated room controllers
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Product overview S-Bus and LonWorks® room controller
S-Bus
L
on
W
orks
System catalogue product
families PCD7
Power supply
230 VAC
+10%/–15%
230 VAC
+10%/–15%
24 VAC
+10%/–10%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
230 VAC
+10%/–15%
Inputs
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Digital inputs
1× window
contact and
1× multi-
functional
1× window
contact and
1× multi-
functional
1× window
contact and
1× multi-
functional
1× window
contact and
1× multi-
functional
4× multi-
functional
1× window
contact and
1× multi-
functional
4× multi-
functional
4× multi-
functional
4× multi-
functional
Operating state response
Yes
Yes
Yes
Yes
Yes
Yes
Yes
---
Yes
Analogue inputs 0…10 VDC
---
1×
0…10 VDC
1×
0…10 VDC
1×
0…10 VDC
---
---
1×
0…10 VDC
2×
0…10 VDC
1×
0…10 VDC
Temperature sensor
1× NTC 10
kOhm
1× NTC 10
kOhm
1× NTC 10
kOhm
1× NTC 10
kOhm
1× NTC 10
kOhm
1× NTC 10
kOhm
1× NTC 10
kOhm
2× NTC 10
kOhm
1× NTC 10
kOhm
Setpoint value adjuster
(10 kOhm potentiometer)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
---
Yes
Outputs
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Digital outputs TRIAC
2× 230 VAC
(total max.
800 mA)
2× 230 VAC
(total max.
800 mA)
2× 24 VAC
(total max.
800 mA)
2× 24 VAC
1)
2× 230 VAC
(total max.
800 mA)
2× 230 VAC
(total max.
800 mA)
2× 24 VAC
1)
4× 230 VAC
(total 2× max.
800 mA)
2× 230 VAC
(total max.
800 mA)
Relay outputs 3-level
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
1× 230 VAC
(3 A)
---
1× 230 VAC
(3 A)
Relay outputs 1-level
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
1× 230 VAC
(10 A)
2× 230 VAC
(10 A)
1× 230 VAC
(10 A)
Analogue outputs (total max. 2 mA)
---
2× 0…10 VDC 2×
0…10 VDC
2×
0…10 VDC
---
2×
0…10 VDC
2×
0…10 VDC
2×
0…10 VDC
2×
0…10 VDC
Analogue outputs with additional 24 VAC
power supply
---
---
Yes
Yes
1)
---
---
Yes
1)
---
---
Extension modules
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Light modules
Yes
Yes
Yes
Yes
---
Yes
4)
---
Yes
2)
---
Shade modules
Yes
Yes
Yes
Yes
---
Yes
3)
---
---
---
Possible applications
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Electrical heating only
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 pipes for heating or“changeover”
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 pipes for cooling or“changeover”with
electric heating
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4 pipes for heating and cooling
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4 pipes for heating and cooling
and electric heating (secondary)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
4 pipes for heating and cooling
and electric heating (primary)
---
---
---
---
Yes
Yes
Yes
Yes
Yes
2 × 2 pipes for heating, cooling
or“changeover”
Yes
Yes
Yes
Yes
---
---
---
---
---
RIO
Yes
Yes
Yes
Yes
---
---
---
---
---
Direct control of outputs
---
---
---
---
Yes
---
Yes
---
Yes
Special functions
L600-1
L601-1
L603-1
L604-1
L610
L611
L614*
L615*
L616*
Air quality control (CO
2
)
Yes
Yes
Yes
Yes
---
---
Yes
---
Yes
Master / Slave
Yes
Yes
Yes
Yes
---
---
---
---
---
Application examples:
Fan coil, chilled beam, air quality control (combined with heating and second level cooling
(radiator/cooling ceiling-, underfloor heating/cooling ceiling combination, changeover operation (e.g. for cooing/heating ceiling), VAV
1)
PCD7.L6x4-1: The total power consumption of valves may not exceed max. 7W, output voltage: 24 VAC; –15% / +35%.
2)
Without automatic function
3)
Without blind slats rotation
4)
Without dimmers
Controlled valves and required I/O
Thermal valve
: 1 digital output (TRIAC PWM)
0…10 V valve
: 1 analogue output (0…10 VDC)
3-point valve
: 2 digital outputs (TRIAC PWM)
6-way valve
: 1 analogue output (0…10 VDC)
can only be connected to one 6-way valve
Controlled drives and required I/O
VAV-drive
: 1 analogue output (0…10 VDC)
3-stage fan
: 1 relay output 3-stage
Fan with variable speed
: 1 analogue output (0…10 VDC)
PCD7.L601-1…L604-1 and PCD7.L614…L616 devices only
Electric heating
: 1 relay output 1-stage
*