PP26-215 EN12a SBC System catalogue 2015/2016 - page 108

108
saia-pcd.com
PCD
7D
Operation and monitoring
2.8
Overview of semi-graphic displays
4 lines × 16 chars
8 lines × 20 characters with graphics capability
Display
PCD7.D170
PCD7.D230
PCD7.D231
PCD7.D232
Colours
Mono
Mono
Mono
Mono
Display type
Text
Graphic
Graphic
Graphic
Lines × characters
4 lines × 16 chars
8 lines × 20 chars
8 lines × 20 chars
8 lines × 20 chars
Resolution
––
128×64 pixels
128×64 pixels
128×66 pixels
Background lighting
LED on/off
LED on/off
LED on/off
LED on/off
Character size (W×H)
3×4.7 mm
2.5×3.5 mm
2.5×3.5 mm
2.5×3.5 mm
Character set
ASCII+special
charsE,D,F,Sca
ASCII (West European)
and Cyrillic
ASCII (West European)
and Cyrillic
ASCII (West European)
and Cyrillic
Keyboard
Total keys
5
1 dial knob
10
25
Function keys and buttons
5 F keys
4)
or 5 keys
––
5 F keys or 5 keys
8 F keys+num. Keyboard
Key autorepeat
Yes
No
Yes
Yes
Buzzer
No
Yes
Yes
Yes
LED status
No
No
No
8
Memory
(PCD)
depending on PLC
depending on PLC
depending on PLC
depending on PLC
Clock
on PLC
on PLC
on PLC
on PLC
Interfaces
RS-232
RS-232/422/485
RS-232/422/485
RS-232/422/485
Log
Point to point
Point to point
Point to point
Point to point
Programming software
HMI editor
2)
HMI editor
HMI editor
HMI editor
Graphic display options
No
Yes
1)
Yes
1)
Yes
1)
Autorepeat function
Yes
––
Yes
3)
Yes
3)
Commands for controlling the function keys
Yes
4)
––
Yes
3)
Yes
3)
LED control commands
––
––
––
Yes
3)
Buzzer control commands
––
Yes
3)
Yes
3)
Yes
3)
General specifications
Supply voltage
24 VDC ±20%
24 VDC ±20%
24 VDC ±20%
24 VDC ±20%
Protection type (front)
IP65
IP54
IP65
IP65
Dimensions (W×H×D) [mm]
120×110×45
115×125×45
115×125×45
115×125×45
Cut-out (W×H) [mm]
109×99
99×109
99×109
99×109
1)
with RS-232 RTS/CTS, XON/XOFF reduced, RS-422 XON/XOFF reduced
2)
only with "shift key" setup mode
3)
not with FTP mode (RS-485)
4)
function keys are not supported by the HMI editor
Text information can be displayed on semi-graphic text panels and, depending on the model, graphic elements may also be displayed.
As these semi-graphic text panels do not have their own memory, all information to be displayed is transferred from the automation
station to the panel for display as and when required.