If a PCD is connected to the PC via USB cable, the new firmware PCD3 V010 and PCD2.M480 V020 do send a unique ID in their StringVendorRequest (iSerialNumber). This has to be done this way because it's the only way to distinguish between several devices with the same VID/PID (VendorID/ProductID) in a USB bus system.
. The PCD7.R-SD256, PCD7.R-SD512 and the PCD7.R-SD1024 can be inserted into an SD card module PCD3.R600 or PCD2.R6000. The SD card module can be plugged in an I/O slot on the PCD3.Mxxxx CPU (or in case of the PCD2.R6000, in one of the first 4 I/O slots of the PCD2.M5540. For further information regarding the handling of the file system on the PCD3 and the PCD2.M5xx0 and the access of the FTP- or [...] PCD7.R-SDxxx SD Flash memory card with file system for SBC PCD3
Standby Controller CPU base units for 4 plug-in I/O modules - Saia PCD3.M6 series PCD3 Standby processor unit with 2 Ethernet TCP/IP and Co-processor for Standby operation, web and FTP server, file system, CPU with 2 MByte user program, 1 MByte SRam extension memory, 128 MByte user Flash memory with file system, clock (RTC), data protection 1-3 years, USB port for PG5, up to 1024 I/O, 2 interrupt inputs, RS-485 for Profi-S-Net/MPI/S-Bus
CPU base units for 4 plug-in I/O modules - Saia PCD3.M6 series PCD3 processor unit with Profibus DP Master and Ethernet TCP/IP, web and FTP server, file system, CPU with 2 MByte user program, 1 MByte SRam extension memory, 128 MByte user Flash memory with file system, clock (RTC), data protection 1-3 years, USB port for PG5, up to 1024 I/O, 2 interrupt inputs, RS-232, RS-485 for Profi-S-Net/MPI/S-Bus
. The PCD7.R-SD256, PCD7.R-SD512 and the PCD7.R-SD1024 can be inserted into an SD card module PCD3.R600 or PCD2.R6000. The SD card module can be plugged in an I/O slot on the PCD3.Mxxxx CPU (or in case of the PCD2.R6000, in one of the first 4 I/O slots of the PCD2.M5540. For further information regarding the handling of the file system on the PCD3 and the PCD2.M5xx0 and the access of the FTP- or [...] PCD7.R-SDxxx SD Flash memory card with file system for SBC PCD3
If once the Software Watchdog is configured on a PCD2.M150, the system can't be started any more until the FW will be changed to either an older version (not recommended) or to the latest version 0E3 (recommended)!
Why do I get wrong values when reading a PCD2/3.W340 with media mapping? (FAQ #101416) PCD2.M5xx0 and the PCD3 [...] by the media mapping for Ni1000 sensors which are connected to a PCD2.W340 or a PCD3.W340 installed on a PCD3 or a PCD2.M5 is not correct with firmware version 1.10.16. Reason The firmware did [...] On the master PCD the I/O mapping to Register 4096 until Register 16'383 for RIO-networks (Profibus DP or Profi-S-I/O) doesen't work on PCD3 and PCD2.M480 and PCD2.M5xx0 systems with firmware version 1
Why do I get wrong values when reading a PCD2/3.W340 with media mapping? (FAQ #101416) PCD2.M5xx0 and the PCD3 [...] by the media mapping for Ni1000 sensors which are connected to a PCD2.W340 or a PCD3.W340 installed on a PCD3 or a PCD2.M5 is not correct with firmware version 1.10.16. Reason The firmware did [...] On the master PCD the I/O mapping to Register 4096 until Register 16'383 for RIO-networks (Profibus DP or Profi-S-I/O) doesen't work on PCD3 and PCD2.M480 and PCD2.M5xx0 systems with firmware version 1
PCD3 or a PCD2.M5540 can be used. On the other hand there is no problem using the newer FT1.2 protocol which is supported by all RS232 interfaces of the PCD3 and the PCD2.M5540. Supported communication interfaces for EIB/KNX driver The table below shows the supported communication interfaces for connecting an EIB coupler to PCD3-, PCD2.M5540 and PCD1.M2120 systems. On other systems (e.g. PCD2.M170) all RS232 interfaces can be used for connecting an EIB/KNX coupler. CPU type PCD3.M5/6xx0 - PCD2.M5540 PCD3.Mxxx0 PCD3.Mxxx0 PCD2.M5540 PCD1.M
...7500 Ohm, 0...300 kOhm 4 analog outputs 12 bit, 0...10 V (3 mA max.) 3 interfaces: RS-485 (S-Bus), USB & NFC (Service) PCD1.G3601-C15: With auxiliary RS-485 interface [...] COSinus FW 1.28.37 was released as maintenance version for the systems: - PCD1.M0xx0/M2xx0, PCD2.M4x60, PCD3.Mxx60, PCD3.M6880 and PCD3.T665/T666/T668 . In June 2017: the COSinus FW 1.28.16 was introduced into production for the systems: - PCD1.M0xx0/M2xx0, PCD2.M4x60, PCD3.Mxx60, PCD3.M6880 and PCD3.T665/T666/T668 . the BACnet and LonIP FW 1.28.16 was put into production