31
saia-pcd.com
PCD
3
5540
F
1
2
1
Saia PCD3.M
F
1
2
1
F
2
1
0
Read Int Ind
ref:Modbus
Enable
Error
Number
Add R 500
Func
RemAdd
Automation stations – Saia PCD3
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Communication interfaces of Saia PCD3.Mxxxx controllers
In addition to the interfaces that the Saia PCD3 has onboard, the interface functions can also be expanded using various slots.
Numerous protocols are therefore supported by the PCD3. For the majority of protocols, the physical bus specifications are offered
as a plug-in module. If this is not the case, the bus can be connected via an external converter.
Modem communication
with the PCD
S-Bus
Modbus
JCI N2-Bus
KNX® S-Mode/EIB
(with external converter)
Physical interfaces for specific protocols
Module Specifications
Slot
Electrical
isolation
Internal current draw
5V +V (24 V)
I/O connec-
tor type
1)
PCD3.F180 Belimo MP-Bus, for connecting up to 8 drives on one line
I/O 0
---
15 mA
15 mA
A
PCD3.F215 BACnet® MS/TP or freely programmable
I/O 0…3
---
110 mA
---
2× K
PCD3.F240 L
on
W
orks
® interface module exclusively for PCD3.M5x6x
I/O 0…3
---
90 mA
---
A9
PCD3.F261 DALI
I/O 0…3
---
90 mA
---
A
PCD3.F270 M-Bus 240 nodes
I/O 0…3
---
70 mA
8 mA
A
PCD3.F271 M-Bus 20 nodes
I/O 0…3
---
70 mA
8 mA
A
PCD3.F272 M-Bus 60 nodes
I/O 0…3
---
70 mA
8 mA
A
PCD3.F273 M-Bus 120 nodes
I/O 0…3
---
70 mA
8 mA
A
PCD3.F281 Belimo MP-Bus with slot for PCD7.F1xxS modules
I/O 0…3
---
90 mA
15 mA
2× K
1)
Plug-in I/O terminal blocks are included with I/O modules. Spare terminals, ribbon connectors with system cables and separate terminals are ordered as accessories
(see pages 34 and 56).
Fully programmable physical interfaces
Module Specifications
Slot
Electrical
isolation
Internal current draw
5V +V (24 V)
I/O connec-
tor type
1)
PCD3.F110 RS-422 with RTS/CTS or RS-485, with line termination
resistors that can be activated
I/O 0
---
40 mA
---
A
PCD3.F121 RS-232 with RTS/CTS, DTR/DSR, DCD
I/O 0
---
15 mA
---
A
PCD3.F150 RS-485 with termination resistors that can be activated
I/O 0
●
130 mA
---
A
PCD3.F210 RS-422/RS-485 plus PCD7.F1xxS as option
I/O 0…3
---
110 mA
---
2× K
PCD3.F221 RS-232 plus PCD7.F1xxS as option
I/O 0…3
---
90 mA
---
2× K
System properties required for
PCD3.Fxxx modules:
The PCD3 system has a processor that
serves both the application and the
serial ports. To determine the maximum
communication capacity for each
PCD3.M5xx0 system, consult the infor-
mation and examples provided in
the manual 26-789 for PCD3.M5xx0.
Interface modules for optional insertion in PCD3.F2xx modules
Module
Specifications
PCD7.F110S RS-422 with RTS/CTS or RS-485
(electrically connected), with terminating resistors that can be activated.
PCD7.F121S RS-232 with RTS/CTS, DTR/DSR, DCD suitable for modem, EIB connection
PCD7.F150S RS-485 (electrically isolated),
with line termination resistors that can be activated
PCD7.F180S Belimo® MP-Bus for connecting up to 8 drives on one line
DALI
EnOcean
(with external converter)
M-Bus
BACnet® MS/TP
HMI editor applications with
PCD7.Dxxx text terminals
(RS-232 only)
Protocols supported by PCD3.Mxxxx via FBoxes
PCD3.F1xx for slot 0
Port 1 RS-232
or
RS-422
or
RS-485
or MP-Bus
PCD3.F2xx for slot no. 0…3
PCD3.F221
RS-232
PCD3.F210
RS-422/RS-485
PCD3.F281
MP-Bus
PCD3.F215
BACnet®-MS/TP
PCD3.F261
DALI
PCD3.F27x
M-Bus