BACnet® MS/TP on Saia PCD®
PCD2.F2150 and PCD3.F215
-
Introduction
The communication modules PCD2.F2150 and PCD3.F215 with BACnet MS/TP allow the direct connection of max. two BACnet MS/TP lines and can be plugged on a PCD1.M2, PCD2.M5 or PCD3.
Furthermore these modules are equipped with an RS485 interface and one slot for PCD7.F1xx cards. They are fully compatible with SBC Mode-C and S-Bus communication, so all the usual serial protocols and F-Boxes for F2xx interfaces are supported.
You will always need an BACnet card PCDx.R56x to work with BACnet MS/TP.
Module overview
There exist 2 different module types to be plugged into PCD I/O slot 0..3. |
| ||||
Modules for the PCD1.M2 and PCD2.M5 | |||||
PCD2.F2150 | up to 255 devices | ||||
Modules for PCD3.Mxxx0 | |||||
PCD3.F215 | up to 255 devices |
Documentation
More information about the BACnet MS/TP modules could be found on the systemcatalogue
PCD3.F1xx & PCD3.F2xx - Communication modules
Manual | 26-857 | PCD3.F1xx & PCD3.F2xx - Communication modules |
BACnet Communication with the Saia PCD3 Automation Station
BACnet, Protocol Implementation Conformance Statement (PICS)
Manual | 26-848 | BACnet, Protocol Implementation Conformance Statement (PICS) |
Firmware
PCD3F2xx and PCD2F2xx0
Firmware | 1.04.06 | PCD3F2xx and PCD2F2xx0 |
Current official production firmware version of the PCDx.F2xx (0) modules
1.04.06 | .blk | 0.10 MB | Download |
ApplicationNote F2xx FirmwareUpdate 2011
Firmware | ApplicationNote F2xx FirmwareUpdate 2011 |
Procedure for updating the firmware of a PCD2.F2xx0 or PCD3.F2xx
EN | 0.07 MB | Download |
Good to know
- There is an example of a PG5 project for BACnet MS/TP communication available in the Getting Started area.
- The BACnet MS/TP option is supported from PG5 2.1.100.
- The PCD needs firmware version of 1.20.25 or more recent.
- The usual instructions for RS485 installation must be followed.
- The BACnet Network nr. must be unique. Do not use double network numbers or the local network (0). In case you have BACnet IP and MS/TP networks connected to the same PCD use different network numbers for the two networks.
- Baudrate must be the same for all devices, BACnet MS/TP does not demand autobauding!
- Amount Master per Network max. 126 + the modul itself
- Take care about the BACnet Networklayer configuration. Details you can fnd in the Online Help of the BACnet Configurators.
- Telegram lenght for MS/TP is limited to max. 480 Byte.
- When extending existing BACnet projects with BACnet MS/TP, the data link settings must be transferred from the Saia BACnet Configurator to the Saia Device Configurator. The BACnet data link settings of the Device Configurator have priority!
PCD2 / Fxxx
- Are the LonWorks devices PCD2.F240, PCD3.F2400 and PCD7.R582 still available? (FAQ #102064)
- Does the PCD support the MP-Bus light protocol and it’s possible connect up to 16 Belimo devices to one MP-Bus line? (FAQ #102016)
- It’s possible to connect more than 8 MP-Bus devices on a MP-bus line (F180 or F280/F280 card)? (FAQ #102015)
- Why the configuration of the DALI devices over PCD2.F2610 or PCD3.F261 and the F-Box ‘Dali Cfg Manger’ does not work correctly? (FAQ #101900)
- Why does my RS-232 S-Bus communication not work with the PCD2.F2xx0 and PCD3.F2xx module? (FAQ #101775)
- Why do I get the error "Missing value" when reading some M-Bus devices? (FAQ #101762)
- Incompatibility of PCD2 /PCD3.F27x(0) and "Hydrometer M-Bus Receiver 868" (FAQ #101717)
- Why can't I read data from a CALEC aquametro energy master device? (FAQ #101710)
- How to Download a Firmware to a PCD2.F2xxx or PCD3.F2xx Module (FAQ #101688)
- What is new in the SBC M-Bus library 2.7.006? (FAQ #101604)
- Why do some M-Bus devices not work on all ports of a PCD2.M5 or a PCD3? (FAQ #101382)
- A PCD2.W3x0 conflicts with a PCD2.F2xx0 or a PCD2.R6000 on a PCD2.M5xxx (FAQ #101262)
- Communication in Bus Terminal topology doesn't work on PCDx.F2xx Module! (FAQ #101091)
- Different handling of the TBSY flag (in MC mode) between PCD3 / PCD2.M5 and older systems (FAQ #100655)
PCD3 / Fxxx
- Are the LonWorks devices PCD2.F240, PCD3.F2400 and PCD7.R582 still available? (FAQ #102064)
- Why are the inputs and outputs of a PCD3 systems not switched on and off correctly, or switched on and off randomly, or the I/O status not detected correctly in the PLC? (FAQ #102063)
- Does the PCD support the MP-Bus light protocol and it’s possible connect up to 16 Belimo devices to one MP-Bus line? (FAQ #102016)
- It’s possible to connect more than 8 MP-Bus devices on a MP-bus line (F180 or F280/F280 card)? (FAQ #102015)
- Why the configuration of the DALI devices over PCD2.F2610 or PCD3.F261 and the F-Box ‘Dali Cfg Manger’ does not work correctly? (FAQ #101900)
- PCD3.F27x and PCD2.F27xx M-Bus is not always short cut protected! (FAQ #101870)
- Why does my RS-232 S-Bus communication not work with the PCD2.F2xx0 and PCD3.F2xx module? (FAQ #101775)
- Why do I get the error "Missing value" when reading some M-Bus devices? (FAQ #101762)
- Incompatibility of PCD2 /PCD3.F27x(0) and "Hydrometer M-Bus Receiver 868" (FAQ #101717)
- Why can't I read data from a CALEC aquametro energy master device? (FAQ #101710)
- How to Download a Firmware to a PCD2.F2xxx or PCD3.F2xx Module (FAQ #101688)
- What is new in the SBC M-Bus library 2.7.006? (FAQ #101604)
- Why do some M-Bus devices not work on all ports of a PCD2.M5 or a PCD3? (FAQ #101382)
- Incompatibility of PCD7.F121 with PCD2.F2xxx / PCD3.F2xx (FAQ #101380)
- Is Modbus supported by Saia PCD®s? (FAQ #101270)
- Communication in Bus Terminal topology doesn't work on PCDx.F2xx Module! (FAQ #101091)
- Why does the communication on the PCD3.F281 not work? (FAQ #101090)
- Where can I plug flash memory modules on a PCD3 CPU? (FAQ #101027)
- Why does my S-Bus communication with an PCD3.F2xx module show a diagnostic error? (FAQ #101011)
- Is it possible to have more than one MP-Bus master in a Fupla File? (FAQ #100958)
- Why is it no more possible to build an old Belimo MP-Bus project with PG5 1.4.300? (FAQ #100957)
- Supported PCD communication ports for EIB/KNX driver (FAQ #100792)
- Callback of PCD7.R500 module (FAQ #100783)
- Why are all MP-Bus FBoxes green but all values are zero? (FAQ #100744)
- Can I use the character mode with XON/XOFF protocol on NT-PCD's? (FAQ #100700)
- Why does my PCD3.F180 stop communicating after a certain time? (FAQ #100693)
- Different handling of the TBSY flag (in MC mode) between PCD3 / PCD2.M5 and older systems (FAQ #100655)
- Possible reasons for not working PCD3.F1xx (FAQ #100649)
- Why does a PCD7.F120 not work when used on a PCD3 or a PCD2.M5? (FAQ #100646)
- Conflict between communication module (PCD3.F1xx) and memory module (PCD3.Rxxx) (FAQ #100636)
- PCD3 with MP-Bus interface card PCD3.F180 - Error: No card echo (FAQ #100611)
- Intelligent modules aren't correctly detected on HW version older than "D" (FAQ #100549)
- Serial-S-Bus on RS422 issues (FAQ #100378)
- Label with connection diagramm on PCD3.F150 (first series) can be wrong (FAQ #100350)
- What is the difference between PCD7.F120 and PCD7.F121? (FAQ #100313)
Communication / BACnet
- What are the differences between the COSinus firmwares FW 1.28.11 and FW 1.28.51? (FAQ #102058)
- On a PCD3.M6860 it’s possible to use BACnet on the Ethernet port ETH1 and/or on ETH2? (FAQ #102031)
- How to know if the PCD integrated BACnet stack is running? (FAQ #102021)
- Why after an download of a PG5 2.2.230 project to the PCD, where BACnet revision 14 is used, the application program on the PCD doesn’t work correctly and have a randomly unexpected/unwanted functionality? (FAQ #102013)
- It’s possible to suppress the PCD Alarms on BACnet? (FAQ #101975)
- Why is BACnet no longer working after an update of the BACnet Device Fbox? (FAQ #101886)
- How can I realize schedules that work over midnight? (FAQ #101821)
- How is it possible to analyze an Ethernet Network, especially for BACnet? (FAQ #101795)
- Are there any restrictions about the number of characters for BACnet Objectname and Description? (FAQ #101788)
- Gibt es Beschränkungen bei BACnet Description und BACnet Object Name ? (FAQ #101787)
- Why does the PCD no longer run due to "BNt FAIL AI00006"? (FAQ #101712)
- What are the differences between BACnet firmware 1.10.50 and 1.16.77? (FAQ #101598)
- What are the differences between BACnet firmware 1.10.24 and 1.10.62? (FAQ #101454)
- How can a BACnet Operator Workstation (B-OWS) know that a PCD has been restarted? (FAQ #101452)
- BACnet failure messages (FAQ #101436)
- Why does the DDC Suite FBox "Motor 2-speed" not swich to speed 2 if BACnet is used? (FAQ #101420)
- Why does the BACnet "Upload/Merge" not work on very busy IP networks? (FAQ #101417)
- Why are the outputs not working in my DDC Suite project (with BACnet enabled)? (FAQ #101254)
- Can I run BACnet and LON on the same PCD at the same time? (FAQ #101216)
- Why is there an offset to the current PCD time in the alarming timestamp? (FAQ #101212)
- How it’s possible to know on the BACnet OPC-Server from Cimetrics if a PCD is accessible over BACnet? (FAQ #101131)
- How to know whether the BACnet module is plugged in the PCD2/PCD3 and that the BACnet stack is running? (FAQ #101119)
- How many BACnet objects can be defined per CPU? (FAQ #101118)
- Where can I plug flash memory modules on a PCD3 CPU? (FAQ #101027)
- How can I test my BACnet configuration without the foreign system? (FAQ #101023)
- Why is it not possible to use priority 6 for commandable objects? (FAQ #101017)
- Why is it not possible to use the same PLC Ressources multiple inside of the BACnet configuration. (FAQ #101016)
- Why do I get an EDE Import Error: Unknown Object ? (FAQ #101015)
- Why do I get an EDE Import Error: Cannot read EDE file! Unknown Format ? (FAQ #101014)
- Why is a Schedule not writing to a referenced BACnet Object? (FAQ #101013)
- Why can't I download a BACnet configuration even if I have a PCDx.R56x installed? (FAQ #101010)