No Refresh from State of I/O's from E-Line Rio- Moduls after Fbox Update
FAQ #102001
Fbox Update of the E-Line Library causes Problem withI/O refresh in Fupla
Symptoms
PG5 2.2.140 with E-Line Fbox Library V2.1.100.
After the automatical Fbox Update in the Fupla Editor, the Projekt will be Rebuilded and downloaded into the PCD without Errors.
Checking the Funktions Online, there is no Refresh for the States of Inputs and Funktion for the Outputs visible.
An Kommunikation Error is not indicated.
Reason
An Error in the PG5 2.2.140 does not perform a clean update
Solution
Is described in FAQ 101994
In PG5 2.2.200 the Error is also fixed (coming soon)
Categories
PCD1
PG5 2.2
Fupla
PG5 2.2 / Fupla
PCD1 / E-Line