PP26-215 EN12a SBC System catalogue 2015/2016 - page 47

47
saia-pcd.com
PCD
2
254
70
208
208
142
70
Automation stations – Saia PCD2
5
Switch cabinet
components
4
Consumer
data acquisition
3
Dedicated
room controllers
2
Operation
and monitoring
1
Automation
stations
Saia PCD2.Cxxxx module holder
Up to 7 Saia PCD2.C1000 or Saia PCD2.C2000 module holders can be connected to the Saia PCD2.M5xxx.
This makes it possible to connect up to 64 I/O modules or 1023 digital I/Os. A module holder has space
for 4/8 I/O modules. In addition to Saia PCD2.Cxxxx module holders, all Saia PCD3 module holders can also
be connected.
System properties
Up to 1023 central data points
Numerous module variants
can be plugged in
Mounting is quick and easy
Can be combined with Saia PCD3.Cxxx
module holders
Connections for a power supply
on each module holder
Can be connected below or next
to each other
Dimensions PCD2.C2000
Dimensions PCD2.C1000
A maximum of 7 module holders can be connected to a PCD2.M5xxx. No more than 5 extension cables
may be used for this. PCD3.Kxxx cables are required for the connection between two module holders!
8 I/O-module slots 0
7
Power supply
I/O bus
4 I/O-module slots 0
3
PCD2.C2000
PCD2.C1000
I/O bus for
standard
modules
Ground con-
nection for I/O
modules
I/O 7
I/O 6
I/O 5
I/O 4
I/O 0
I/O 1
I/O 2
I/O 3
I/O 0
I/O 1
I/O 3
I/O 2
I/O bus connections
PCD2.K010
or exten-
sion cable
PCD3.K106
PCD3.K116
I/O bus extension cable
PCD2.K106
A...,37,38,39,40,41,42,43,44,45,46 48,49,50,51,52,53,54,55,56,57,...Z