PCD3 processor unit with Ethernet TCP/IP
Extension cable for PCD2.M4560 to PCD2.Cx000, PCD3.M/T/C to PCD3.Cxx0 or PCD2.C1000/..C2000 to PCD2.C1000/..C2000 (length 1.2 m)
Extension cable for PCD2.M4560 to PCD2.Cx000, PCD3.M/T/C to PCD3.Cxx0 or PCD2.C1000/..C2000 to PCD2.C1000/..C2000 (length 0.7 m)
Connection plug PCD3.M/T/C to PCD3.Cxx0
Input/Output Simulator for PCD3.M/.T/.C (for ex. for test assembly or workshop models)
A hardware conflict on a PCD2.M5xxx between a PCD2.W3x0 plugged to I/O slot 3 and the modules PCD2.F2xx0 and PCD2.R6000 leads to the fact that the communication- and memory modules do not work in this constellation. If the PCD2.W3x0 is removed from the I/O slot 3 the installation is working correctly.
General Cyber Security Enhancements History names with up to 200 characters Signed & Encrypted OPC-UA ommunication to PCD3.M6893 (QronoX-IEC-Controller) Latest Max Pro updates Enhancements [...] Actual version Saia PCD Supervisor 4.12 (version 4.12.0.156.1.3) This version 4.12 does include a complete installation package of the Saia PCD Supervisor Saia PCD Supervisor [...] Product Category Software Saia PCD Supervisor Version overview Saia PCD Supervisor Actual version
. 1-ph. M-Bus Interf. 3-ph. M-Bus Interf [...] supply voltage pins 1L/2L and 3N/4N are inverted. This wrong label is present on the schema of the housing and directly on the pins. Problem When a PCD7.T162 produced before week 22 of 2011 [...] functionality is still the same but the 24V DC need to be connected to the pins 3N/4N and the 0V to 1L/2L. Remark Units of PCD7.T162 produced after 11/22 (30.05.2011) are correctly labelled and
A. Nevertheless it is possible measuring the range 0..20 mA with the analogue input modules for PCD systems. Why do the SBC input modules have a range of 0..20 mA? One advantage of measuring the [...] Product Category Archive Programmable Controller PCD6: CPUs in 19 inch racks Axxx [...] commercially available products. PCD
-Bus Data mode"). Saia PCD® COSinus based systems (PCD2.M480, PCD2.M5xx0 and PCD3) are not concerned. Reason The reason for this behavior is that the PCD/PCS does not correcly answer telegrams where [...] appears if the used firmware on the CPU does not support the "active and non ACK" filter for the S-Web alarming functionality (e.g. a PCD2.M150 with firmware 0D3). Symptom Instead of the [...] to the firmware supporting the according feature (see table below). System minimal FW PCS1.Cxxx 0E3 PCD1.M1x5 0E3 PCD2.M150 0E3