Why can't I send more than 512 bytes using the STXT instruction?

FAQ #101468

In case a text with more than 512 bytes is sent with a firmware older than 1.14.23 the according text has not been sent correctly.

 

Symptom
When sending a text with a length of more than 512 bytes on a PCD3 or a PCD2.M5 with a firmware older than 1.14.23 the text which is sent is not correct.
In case the text to be sent contains sub-texts which are introduced using interpreted text (e.g. the $Lnnnn) and the final length to be sent is more than 512 bytes, the same phenomenon can be observed.

Solution
Please update the firmware of your PCD to version 1.14.23 or later.

 

Categories

PCD2 / _Firmware Classic

PCD3 / _Firmware Classic

Local FAQ Deutschland / SEdit (IL programming)

PG5 2.0 / SEdit (IL programming)

Last update: 28.05.2015 08:20

First release: 21.07.2010 18:02

Views: 41772

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download