Why is the error bit 7 or 8 set when I try to execute a "Backup DB to flash"?
FAQ #101466
In some cases, usually after a lot of backups which have been executed, the error bit 7 (flash task already started) or 8 (flash error) is set with firmware older than 1.14.23.
Symptom
A backup DB to flash (IL instruction "copy TEXT/DB to flash card", SYSWR 3000 or 3100) fails and the error bits 7 and/or 8 are set. This error remains, even after waiting several minutes without re-attempting a backup to flash.
Solution
This problem is corrected in firmware 1.14.23 or later. Please update your PCD firmware in order to solve this problem.
Categories
PCD2 / _Firmware Classic
PCD3 / _Firmware Classic
Local FAQ Deutschland / SEdit (IL programming)
PG5 2.0 / SEdit (IL programming)
Last update: 30.05.2015 21:32
First release: 21.07.2010 17:35
Views: 42809