Why is the Port 3 on the PCD3.M5340 not running correctly in RS 485 mode?
FAQ #100765
The first versions of the PCD3.M5340 controller have been delivered with a firmware that does not support the usage of the RS485 port on port 3.
Problem
The communication RS 485 on port 3 of the PCD3.M5340 is not working correctly.
Reason
Due to a problem in the firmware, the port is not correctly initialized to RS 485.
Solution
Upgrade the PCD3 firmware to version 1.08.23 or higher.
Remark
There is no problem for the usage of the port 3 as RS422 port.