Hoe te wissen opgeslagen itemwaarden worden weergegeven in een PCD7.H104S/SE

FAQ #101930

Als u wilt schrijven/duidelijk de waarde van de teller in de H104S/SE, de F-doos ' H104S/SE Set' moet worden gebruikt.

 

The 'clear' input from the F-Box "H104S/SE read" does clear the stored counter values (which are stored in PCD register) but not the register in the H104S/SE.
If the PCD does read the next time the values from the H104S/SE, then the old values, stored in H104S/SE are copied again in the counter register of the PCD.
Therefore the 'clear' input of the F-Box
"H104S/SE read" can not be used to clear the counter values in the H104S/SE.


To write (or clear) the counter value in the H104SE use the F-Box "H104S/SE Set".

Which register (addresses) must be written, can be found in the datasheet of H104S/SE.