Ondersteunde baudrates en protocollen op een PCD2.M480
FAQ #100355
De seriële poorten van de PCD2.M480 staat toe om te communiceren tot 115 kB/s.
The PCD2.M480 does support the following baudrates:
Serial communication (Serial-S-Bus, Mode C)
Baud rate (kB/s) | |||||||||||
PCD2 Socket | Module | 1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 76800 | 115200 | |
Port # | |||||||||||
0 | On-board | X | X | X | X | X | X | X | X | X | |
1 | A | PCD7.F1xx | X | X | X | X | X | X | |||
1 | A | PCD7.F121 | X | X | X | X | X | X | X | X | X |
2 | B1 | PCD2.F5xx | X | X | X | X | X | X | |||
3 | B1 | PCD2.F5xx | X | X | X | X | X | X | |||
4 | B2 | PCD2.F5xx | X | X | X | X | X | X | |||
5 | B2 | PCD2.F5xx | X | X | X | X | X | X | |||
6 | On-board | X | X | X | X | X | X | X | X | X |
Restrictions:
- For the ports 2,3 and 4,5 following combination of baud rates are not allowed on the same PCD2.F5xx:
19,2 kBaud and 38,4 kBaud - On the port 1 it’s not possible to use the S-Bus party Master mode.
- Mode D is not supported.
Profibus
Supported baudrates | Supported protocols | |||||||||||||
PCD2 Socket | Module | 93,75 kB/s | 187,5 kB/s | 500 kB/s | 1,5 MB/s | 3 MB/s | 6 MB/s | 12 MB/s | Profi-S-Bus | Profi-S-IO Master or Slave | Profibus-DP Master | Profibus-DP Slave | ||
Port # | ||||||||||||||
8 | B2 | PCD7.F750 | X | X | X | X | X | X | X | X | X | |||
9 | B1 | PCD7.F750 | X | X | X | X | X | X | X | X | X | |||
10 | On-board | X | X | X | X | X | X | X |
Remark:
Multi protocol on the same port is supported.
Example:
On the port 10 it’s possible to act at the same time as Profi-S-Bus Master and Slave, Profi-S-IO (Master or Slave) or Profibus-DP Slave.
Restriction:
If the port 10 is used as Profi-S-IO Master, then it’s not possible to act at the same time as Profi-S-IO Slave or Profbius-DP Slave on the port 10.
Ethernet TCP/IP
Baudrate | ||||
PCD2 Socket | Module | 10MB | 100MB | |
Port # | ||||
8 | B2 | PCD7.F650 | X | X |
9 | B1 | PCD7.F650 | X | X |
Remark:
Multi protocol on the same port is supported.
Example: On the port 8 it’s possible to act at the same time as Ether-S-Bus Master and as Ether-S-Bus Slave
Categories
PG5 2.0 / Profibus DP
Communication / Ether-S-Bus
PG5 2.0 / Profi-S-Bus
PG5 2.0 / Serial-S-Bus
PG5 2.0 / Profi-S-I/O
PCD2 / M48x
Last update: 27.05.2015 22:37
First release: 02.05.2005 12:39
Views: 14468