This product is outphased.
Product Category Programmable controller PLC Accessories SO to S-Bus Interface PCD7.H104S [...] PCD7.H104xx S0 converter Documentation Software / Drivers The Fupla libraries installed by default in PG5 1.4.300 and later include the FBoxes for the PCD7.H104S
. Why the RS-485 S-Bus communication between the PCD master and the slave does fail sometime, if FW 1.28.20…1.28.33 is used? (FAQ #102026) It’s possible that the some of the S-Bus telegrams transferred from the PCD S-Bus master to the S-Bus slaves over RS485 are malformed, and the S-Bus slave does reject the request from the master. This could lead to the situation that for example the PCD S-Bus master don’t receive actual values from E-Line RIO’s or that the program download of a PCD program from the PC to a Slave PCD which is
01 0271 0022 fexible cable Note: If the bautrates isn't greater than 187,5 bautes (for ex. Profi S-Bus with PCD3.M3xx / PCD7.D7xx) you can use other more advantegeous cable, especially [...] and connector as the communication speed goes up to 12 Mbautes! Those cable and connectors are used in Profibus DP, FMS, Profis S-Bus, Profi S-IO and MPI! Wiring and Network [...] for the port 3 of the PCD3.M5540 as Serial-S-Bus RS485 connection (Serial-S-Bus) between PCD3.M5540 port 3 (S-Net D-Sub used as RS485 Serial-S-Bus) and PCD2.M5540 port 2 (connector block X
Ether-S-Bus communication or Ethernet communication in general, we recommend using the free software Wireshark ( www.wireshark.org ). This is an open source analyzer (including matching log file creator WinPcap). The Wireshark analyzer is able to dissect Ether-S-Bus from version 1.1 on. For more information please refer to the according FAQ #100569 . Good to know In June 2006 the new
Characteristics of the MP-Bus protocol - No special cable or line termination resistors - Costs saved due to reduced expenditure on cabling and easy handling - Simple commissioning and maintenance - Uncomplicated method for integrating and exchanging actuators - Compatible with BELIMO® actuators using MFT/MFT2 technology
! PCD7.D761 / D763 loses communication on Profi S-Bus! (FAQ #100477) On a Profi S-Bus network when PCD7.D76_ terminals [...] ! How to convert variables from S-Bus to Ether S-Bus driver when changing terminal type? (FAQ #100461) It is possible to convert all the variable from a S-Bus driver to Ether S-Bus driver if an existing project has to be used on another terminal type (e.g. PCD7.D786 convert to PCD7.D786ET)! Hereby the procedure to
A PCD7.D7xx Terminal can access several PCD's in an S-Bus network, it is as well possible to have one gateway station in the network and access PCD's that are located in a subnet. The response timeout has to be adapted accordingly.