connected to PCD3.Mxxx or PCD2.M480 PLC's over Profi S-Bus, the terminal loses the communication after some time and get even frozen. This problem is corrected in the new boot, FW and driver. The PCD8.D81 V 5.09 is needed , the attached files have to be copied in it (see procedure below). It is also necessary to update the PCD3.Mxxx and PCD2.M480 FW with the version PCD3.Mxxx_023.blk / PCD2.M480_$27 or [...] 01 0271 0022 fexible cable Note: If the bautrates isn't greater than 187,5 bautes (for ex. Profi S-Bus with PCD3.M3xx / PCD7.D7xx) you can use other more advantegeous cable, especially
) on Saia PCD® COSinus systems (PCD3, PCD2.M5, PCD1.M2 and PCD2.M480). This phenomenon is based on the internal mechanism how the firmware assigns the port. It has not been observed before the usage of [...] ). The new FBox library for Modbus "Modbus SBC Version" which takes advantage of the Modbus implementation directly in the Saia PCD® COSinus firmware. Available for PCD1.M2, PCD3 and PCD2.M5 with firmware [...] .engiby.ch ) and supported also by PCD systems previous to the PCD3, PCD2.M5xxx and PCD1.M2xxx families (e.g. PCD2.M1x0, PCD2.M480 or PCD1.M1xx). Remarks In order to use the firmware implementation
New FBoxes for "variable fan speed" function, which can only be used with PCD7.L60x-1 controllers from FW SV3.00. Corrections/modifications: Since V2.6.810: - Minimum value for max. Fan limited to step 1 in 'Fan Configuration' and 'Fan Room 3', that no problem with deactivation of the cooling or heating output can be created anymore. (If fan max speed will be set to 0, then a safety function will be activated and the heating output will be deactivated) - Bugfix for M/S-Mode in 'HVC Room' FBox -------------------------------------------------
Package does include the FW for the PCD1.M0, PCD1.M2, PCD2.M5, PCD3.M, pWeb-Panel and the BACnet and LonIP FW. This firmware does support the modules PCD7.W600 and PCD7.R610 Do use at least the PG5 firmware downloader version 2.1.311 or newer (included in PG5 patch 2.1.311 or newer) to prevent the loading of the FW 1.24.xx to a not compatible PCD.
There are firmware depending differences in the handling of the Serial-S-Bus communication diagnosic flags TDIA and RDIA. Those flags are refreshed continuously by older FW versions but not by the Saia PCD® COSinus Classic PCD firmware (used for PCD2.M480 and PCD3 controllers).
5xx0 PCD3.Mxxx0 PCD3.Mxx60 PCD3.M6860 PCD3.M6880 PCD3.T665/T666/T666 PCD7.D4xxxT5F pWeb Panel PCD7.D443WT5F pWeb Panel PCD7.D4xxV VGA MB Panel PCD7.D412DTPF SVGA MB Panel PCD7.D4xxWTPF WVGA MB Panel BACnet FW for PCD1.M2xx0, PCD2.M4x60, PCD2.M5xx0, PCD3.Mxxx0, PCD3.Mxx60 LonIp FW for PCD1.M2xx0, PCD2.M4x60, PCD2.M5xx0, PCD3.Mxxx0, PCD3.Mxx60 Please check the Hardware [...] COSinus FW 1.28.37 was released as maintenance version for the systems: - PCD1.M0xx0/M2xx0, PCD2.M4x60, PCD3.Mxx60, PCD3.M6880 and PCD3.T665/T666/T668 . In June 2017: the COSinus FW 1