COSinus FW 1.24.69 was introduced into production for the systems PCD2.M5xx0, PCD3.Mxxx0. The corresponding BACnet and LonIP firmware is available on the support homepage. In March 2017 the COSinus FW 1.24.67 was introduced into production for the systems PCD2.M5xx0, PCD3.Mxxx0. The corresponding BACnet and LonIP firmware is available on the support homepage. In Mai 2015 the maintenance COSinus FW 1.24.30 was published for the systems PCD1.M0xx0, PCD1.M2xx0, PCD2.M5xx0, PCD3.Mxxx0, PCD3.Mxx60 and PCD7.D4xxxT5F. In February 2015 the COSinus FW 1.24.25 was introduced into
itselfs influences the measurement it has been stated that the precisision is not according to the manual of this PCD7.D290 display (26/841 version 4). The chapters 4.2.3 (Temperature sensor) and 4.2.4 (R.H. sensor) will be adapted accordingly in the next release. 4.2.3 Temperature sensor Temperature sensor used in PCD7.D290 is active and supplies as output a voltage of 10.0 mV/°C; this [...] Product Index Archive PCD7 Dxxx: HMI D290: Text terminal General
. HMI Editor and PCD3.M_ or PCD2.M480: Wrong characters are display instead of value with Format #####! (FAQ #100360) When an element is configured as Integer with the format ##### (without dot) the value of the register is wrongly displayed on the terminal. This is a FW bug in the actual version of the PCD3.M_ and PCD2.M480. This problem occurs with all FW version up to: PCD3.M_ #13 (that means also 010, #11, #12) PCD2.M480 #23 (that means also 020, #21, #22) Solution Please
. Timings Display PCD7.D120 with a PCD3.M5xxx (FAQ #101569) The settings for Clock period High and Clock period low must be 2 / 150 same settings as for the PCD2.M [...] signal display CXG291M4N could be used. Introduction Due to a low demand, the delivery of PCD7.D120 displays will be discontinued in the year 2008 (last order: 31.09.2008). The repair
A. Nevertheless it is possible measuring the range 0..20 mA with the analogue input modules for PCD systems. Why do the SBC input modules have a range of 0..20 mA? One advantage of measuring the [...] Product Index Archive PCD6 Cxxx General [...] . PCD6 Series (obsolete) Documentation
A. Nevertheless it is possible measuring the range 0..20 mA with the analogue input modules for PCD systems. Why do the SBC input modules have a range of 0..20 mA? One advantage of measuring the [...] Product Category Archive Programmable Controller PCD6: CPUs in 19 inch racks Cxxx [...] commercially available products. PCD
a PCD2.M5xx0? (FAQ #101386) No, the PCD4.C225 is not supported by a PCD2.M5xx0 CPU. Due to the higher processing speed of the PCD2.M5 (compared to e.g. a PCD2.M150) it can not be guaranteed that the I/O modules are correctly accessed. Why is this fact not stated in the manual for the PCD4? In the manual for the PCD4 (27/734) there is not information regarding this restriction (it is only stated that a PCD2.M110 can not be used togheter with the PCD4.C225, and that no H-Modules or W1/W2/W3 modules
a PCD2.M5xx0? (FAQ #101386) No, the PCD4.C225 is not supported by a PCD2.M5xx0 CPU. Due to the higher processing speed of the PCD2.M5 (compared to e.g. a PCD2.M150) it can not be guaranteed that the I/O modules are correctly accessed. Why is this fact not stated in the manual for the PCD4? In the manual for the PCD4 (27/734) there is not information regarding this restriction (it is only stated that a PCD2.M110 can not be used togheter with the PCD4.C225, and that no H-Modules or W1/W2/W3 modules
inputs. To fill this gap we offer interrupt inputs and dedicated I/O modules. For OEM applications we can offer attractive customized solutions. Interrupt inputs on PCD2.M120 , PCD2.M150 , PCD2.M170 , PCD4.M170 (1kHz unidirectional max.) Counter modules PCD2.H100 (simple, 20kHz max.), PCD2.H110 (versatile, 100kHz max.), PCD4.H120 (versatile, 166kHz max.) SSI module PCD2.H150 Interrupt inputs on PCD2.M157 , PCD2.M177 (5kHz bidirectional or unidirectional max.) Counter modules PCD2.H100 (simple, 20kHz max.), PCD2.H110 (versatile, 100
Ethernet port (PCD7.F655 or the integrated Ethernet ports on the PCD1.M0/M2, PCD2.M5 and PCD3 and all Panels with Ethernet ports) are not designed for this purpose. Possible solution to connect PCD [...] firmwares 1.16.xx have been introduced. The concerned systems are the PCD1.M2xx0, PCD2.M5xx0, PCD3.Mxxx0 and PCD3.Mxx60. This bug is now fix and it is once again possible to use the MPI communication with [...] ) on Saia PCD® COSinus systems (PCD3, PCD2.M5, PCD1.M2 and PCD2.M480). This phenomenon is based on the internal mechanism how the firmware assigns the port. It has not been observed before the usage of