Ether S-Bus communication is no more working after the update to PG5 2.1.210

FAQ #101867

After a PG5 Update to the version PG5 2.1.210, the Ether S-Bus Communication is no more working.

The S-Bus client and server functionality is disabled in the Device Configurator.

 

Reason:

In the TCP/IP Setting Table in the column "0" there is no entry.

§Ix101578§

This entry is generated from the Device Configurator.
You can find it under Ether S-Bus, when you click on the row Ethernet in the onboard communication.

§Ix101579§

Solution:
The setting should be "default" and when you open it, Client and Server should be checked.

§Ix101580§

After saving this settings in the device configurator, the TCP/IP setting Table should be corrected.
To activate the new settings it's necessary to compile and download the project in to the PCD.

§Ix101581§

 