Problem
After compiling and download of a LON IP project with PG5 2.1.100.0, the error LONIP FAILED 1007 is shown in the history of the PCD and the PCD goes to halt.
This problem is due to a bug in the LONIP configurator of PG5 2.1.100.
With PG5 2.0.220.200 this problem was not yet present.
Solution
Install the patch 1 for PG5 2.1 that can be downloaded from the Support homepage in the section Software / PG5 2.1 Suite.