Profi S-Bus doesn’t work on the PCD1.M2xx0
FAQ #101809
Due of an error of PG5 2.0 and PG5 2.1 it’s not possible to configure on the device configurator correctly the Profi-S-Bus of the PCD1.M2xx0.
The device configurator uses the port 2 for Profi-S-Bus, instead to use the port 0.
The error is fixed on PG5 2.1 version PG5 $2.1.047
Categories
PCD1 / M2xx0
Last update: 30.05.2015 17:41
First release: 20.12.2012 10:11