What is the maximum of exchanged data over Profibus DP on a PCD?

FAQ #101642

The maximum of exchanged data over a Profibus DP interface (or Profi-S-I/O) interface is depending on the system (the amount is not the same for a PCD7.F750 or a PCD3).

 

PCD7.F750 placed on a PCD2.M1x0 (non SBC-NT)
The Profibus DP manual states that the maximal amount of exchanged data per PCD7.F750 is 2942 bytes.

PCD3, PCD2.M5 or PCD2.M480 and PCD1.M2 (SBC-NT)
The limitation mentioned above does not apply for SBC-NT systems where the maximal amount of exchanged data is 2048 bytes.

 

Categories

PG5 2.0 / Profibus DP

PG5 2.0 / Profi-S-I/O

Last update: 25.05.2015 04:44

First release: 29.07.2011 05:21

Views: 7015

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download