Remark when importing a PG5 1.4 project into PG5 2.0.150 with patch 4(a)

FAQ #101628

Due to a bug in PG5 2.0.150.400 (PG5 2.0 with patch 4 or patch 4a) the original projects from PG5 1.4 are modified during the import of the project.

 

Symptom
After a PG5 1.4 project has been imported into PG5 2.0.150.400 (menu "Project" --> "Import..."), it is no longer possible to open the project in PG5 1.4.

Reason
The original files in the project folder from PG5 1.4 are modified during the import due to a bug in patch 4 of PG5 2.0.150

Solution

  • Please update to your PG5 2.0.150 to patch 5 (PG5 2.0.150.500) or more recent.
  • In case you do have a project which was modified by the import of PG5 2.0.150 with patch 4:
    - launch the executable "fix1080.exe" from the installation folder of PG5 2.0.150 with patch 5 applied
    - browse to the modified project and click "modify"

Remark
In case you do not have the possibility to update to patch 5 or more recent: Do not import the project directly, but first create a backup from the PG5 1.4 project and restore this backup file with PG5 2.0. 

 

Categories

PG5 2.0 / Project Manager

Last update: 30.05.2015 01:03

First release: 27.06.2011 14:57

Views: 24557

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download