Points to be considered when using the Room controllers L60x in "Stand alone Mode"

FAQ #101514

If the controller is used without an S-Bus connection and there is a power supply interrupt, the occupancy mode (OccMode) of the controller is initialized with the value 1 (unoccupied) after restart.

 

What to do if I need another mode after restart?

  • If the controller is supposed to run in Stand-By mode (OccMode 2), a little workaround is needed:
    In the adjust window of the Config-FBox the parameter “Dead band reduced mode” and the “Dead band standby mode” need to contain the same values. (Or it can be written directly in the register 4)

    image

    (And the “Coasting Comfort Mode x10min” has to be left on the initial value 0 => register 0)

    image
     
  • If the controller is supposed to run in Comfort Mode (OccMode 0), a little workaround is needed:
    In the adjust window of the Config-FBox the parameter “Dead band reduced mode” and the “Dead band comfort mode” need to contain the same values. (Or it can be written directly in the register 4)

    image

The FBox libraries required can be downloaded from the support website, the version of the libraries must be:

  • For PG5 1.4:
    PCD7.L60x RoomController FBox library version 2.5.166 or later
  • For PG5 2.0:
    PCD7.L60x RoomController FBox library version 2.6.166 or later