Why is the PCD7.L60x occupancy output switching from 1 to 0 when changing a setpoint value?

FAQ #101455

The output of the L60x Room Controller FBox switches from 1 to 0 when the temperatur setpoint is modified. This phenomenon appears on the new hardware V2.0 and SW 1.12!

 

Symptom
The output of the L60x Room Controller FBox switches from 1 to 0 when the temperatur setpoint is modified. This phenomenon appears on the new hardware V2.0 and SW 1.12!

Reason
The software version 1.12 does not identically treat the state of the occupancy input in case of changed setpoints (written by the PCD).

Solution
A new FBox library version takes this different behaviour of the room controller into account; please use the below mentioned FBox library which is available on the support site!
FBox library which solves this issue:

  • PG5 2.0: 2.6.151 or later
  • PG5 1.4: 2.5.101 or later