Why do I get wrong values when reading a PCD2/3.W340 with media mapping?

FAQ #101416

PCD2.M5xx0 and the PCD3.Mxxx0 systems equipped with firmware 1.10.16 did not correctly calculate the temperature values of NI1000 temperature sensors measured with PCD2/3.W340 input modules.

 

Symptom
The temperature read by the media mapping for Ni1000 sensors which are connected to a PCD2.W340 or a PCD3.W340 installed on a PCD3 or a PCD2.M5 is not correct with firmware version 1.10.16.

Reason
The firmware did not correctly convert the measured signals to the according temperature.

Solution
Please update the firmware of your PCD to version 1.10.51 or later.

 

Categories

PCD2 / Wxxx

PCD3 / Wxxx

PG5 2.0 / Device Configurator

Last update: 31.05.2015 12:51

First release: 06.05.2010 16:56

Views: 34235

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download