How many HDLog trend variables can I log into one single CSV-file?

FAQ #101341

You can extend the HDLog FBox to log a maximum of 10 trend variables. If you want to log more than 10 trends, you'll have to place several HDLog FBoxes.

 

The HDLog FBox you place has to get a unique reference name. Because the CSV-file, that contains the maximum of 10 trend variables, is combined to this unique name. If you want to log more than 10 trends, you'll have to place an additional HDLog FBox with another unique name referenced. Because these additional 10 trends are logged into a second CSV-file combined to the second unique name. This means, that in one single CSV-file you can log a maximum of 10 trends.

 