Why after a SASI instruction for Profibus FMS communication, the error flag of the PCD is set to high?
FAQ #101218
If the Control interval (ASS/ABI-CI) is set to 0 then the error flag will be set to high after the SASI instruction.
The Control interval (ASS/ABI-CI) is defined on the following menu of the PG5 Profibus-FMS configurator:
Edit Station, Channel List, Header
Categories
PG5 2.0 / Profibus FMS
Last update: 31.05.2015 22:07
First release: 22.05.2009 14:00
Views: 3425