Why it’s not possible to make the binding with the LonMaker to a PCS1?
FAQ #101132
If a PCS1 does use at the same time a serial communication with > 9’600 baud and the user wants to make a binding with the LonMaker then it’s possible that the binding will not succeed and on the LonMaker there is an error message:
“The device is application less or is not associated with a program record”
To solve the problem and to be able to make the binding either you have to switch off the serial communication or to use a baudrate <= 9'600 baud.
The reason of the problem is, that the PCS1 has not enough CPU power to perform simultaneously a Lon binding and a serial communication with > 9'600 baud.
Categories
Communication / LON (FTT10)
Last update: 01.06.2015 01:27
First release: 10.02.2009 13:54
Views: 1862