Is possible to use two TCP/IP modules on a PCD CPU?
FAQ #100785
Yes, the PCD2.M480 is able to handle two TCP/IP (PCD7.F655) modules.
If there is the need to have two independent TCP/IP modules on one PCD, then you have to use the PCD2.M480 CPU. On the PCD2.M480 it is possible to install two PCD7.F655, one on the emplacement B1 and one on the emplacement B2.
The PCD2.M480 does support the routing mechanism of TCP/IP request between the two cards only for the direction:
TCP/IP card on emplacement B1 to TCP/IP card on emplacement B2.
Categories
PCD7 / Fxxx
Communication / Ether-S-Bus
PCD2 / M1xx
PCD2 / M48x
Last update: 21.05.2015 11:09
First release: 16.10.2007 08:45