Why are all MP-Bus FBoxes green but all values are zero?

FAQ #100744

There is a problem in the Belimo library distributed togehter with PG5 1.4.200.

 

Symptom
All MP-Bus F-Boxes are green but no values are beeing transmitted.

Reason
There is a problem in the Belimo library 2.5.140 which is installed together PG5 1.4.200

Solution
A correction for this problem has been implemented in the MP Bus library version 2.5.142. The easyest way for resolving the problem is updating to PG5 1.4.300 or higher (the latest PG5 version is available on the supportsite www.sbc-support.ch in the section "Product info" --> "Software" --> "PG5").

 