Why are all MP-Bus FBoxes green but all values are zero?
FAQ #100744
There is a problem in the Belimo library distributed togehter with PG5 1.4.200.
Symptom
All MP-Bus F-Boxes are green but no values are beeing transmitted.
Reason
There is a problem in the Belimo library 2.5.140 which is installed together PG5 1.4.200
Solution
A correction for this problem has been implemented in the MP Bus library version 2.5.142. The easyest way for resolving the problem is updating to PG5 1.4.300 or higher (the latest PG5 version is available on the supportsite www.sbc-support.ch in the section "Product info" --> "Software" --> "PG5").
Categories
PCD2 / Txxx
PCD3 / Fxxx
PG5 2.0 / MP-Bus
Last update: 29.05.2015 06:33