Why are all MP-Bus FBoxes green but all values are zero?

FAQ #100744

There is a problem in the Belimo library distributed togehter with PG5 1.4.200.

 

Symptom
All MP-Bus F-Boxes are green but no values are beeing transmitted.

Reason
There is a problem in the Belimo library 2.5.140 which is installed together PG5 1.4.200

Solution
A correction for this problem has been implemented in the MP Bus library version 2.5.142. The easyest way for resolving the problem is updating to PG5 1.4.300 or higher (the latest PG5 version is available on the supportsite www.sbc-support.ch in the section "Product info" --> "Software" --> "PG5").

 

Categories

PCD2 / Txxx

PCD3 / Fxxx

PG5 2.0 / MP-Bus

Last update: 29.05.2015 06:33

First release: 24.07.2007 15:05

Views: 5743

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download