Value-string translation for states of FBox "Call SMS"

FAQ #100709

In the adust window of the FBox "Call SMS" the actual- and the "last end"-status of the SMS transmission is shown if PG5 is online with the PCD. These states are directly shown as string for better readability. This FAQ contains the according values of the register in the PCD.

 

 

When visualizing this status on a SCADA system such as Visi.Plus, the translation form the read value to the according string must be done. The tables below shows the possible values and their meanings (strings):

 

"Last End" status of "Call SMS" FBox
  Value String
  0 Standby
  4 Error
  5 Lost
  6 Abort
  9 End
  20 End OK
  21 Error Code
  22 End No OK

 

"Actual Status" of "Call SMS" FBox
  Value String
  0 Standby
  2 Connect
  4 Error
  5 Lost
  6 Abort
  9 End
  19 Waiting
  40 Command
  322 Call SMS
  800 Call
  900 Aborted

 

 

Categories

Local FAQ Deutschland / Modem library

Last update: 29.05.2015 13:04

First release: 18.04.2007 13:33

Views: 2336

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download