The PCD goes in HALT with a BUS ERROR if many accesses to the WebServer are executed
FAQ #100658
After a few houres or days the PCD3 goes in HALT with a BUS ERROR.
Problem
The PCD3 goes in HALT with a BUS ERROR after a few hours or days. After a power off / on it works again for a while
Reason
This can happen if many accesses to the WebServer are executet and a firmware <030 or <$2A is in use.
Solution
Update the firmware to 030 or $2A
Categories
S-Web Technology
Last update: 30.05.2015 01:15
First release: 09.01.2007 10:07