Problem with LON communication and "Alias" support (PCD7.F800 / F802)

FAQ #100531

Concerned PCD systems: All LON supported PCD systems

 

Problem

The PCD freezes itself for all manual or automatic program function. The debugger tool can still opened but the actual program condition accept no manipulation anymore.

 

When occurs the problem: With LON communication and “Alias” support. The problem will only appear with the amount of approximately 200 active SNVT connections (LON bindings).

 

Solution
Exchange the firmware of the PCD system

 

The problem is solved in the firmware of the following systems:

System type:
Recent firmware
New official
PCD1.M120/M130
The firmware will not be updated
 
PCD1.M1x5
PCD1M1x5_#A4.blk
0A4
PCD2.M110/M120
The firmware will not be updated
 
PCD2.M150
PCD2M150_#D1
0D1
PCD2.M170
PCD2M170_#21.blk
021
PCS1.C88x
PCS1.C6xx_C8xx__#B3
0B3

Categories

PCD7 / Fxxx

Communication

Last update: 23.05.2015 20:43

First release: 14.02.2006 14:40

Views: 1687

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.