Problem with LON communication and "Alias" support (PCD7.F800 / F802)
FAQ #100531
Concerned PCD systems: All LON supported PCD systems
Problem
The PCD freezes itself for all manual or automatic program function. The debugger tool can still opened but the actual program condition accept no manipulation anymore.
When occurs the problem: With LON communication and “Alias” support. The problem will only appear with the amount of approximately 200 active SNVT connections (LON bindings).
Solution
Exchange the firmware of the PCD system
The problem is solved in the firmware of the following systems:
System type: |
Recent firmware |
New official |
PCD1.M120/M130 |
The firmware will not be updated |
|
PCD1.M1x5 |
PCD1M1x5_#A4.blk |
0A4 |
PCD2.M110/M120 |
The firmware will not be updated |
|
PCD2.M150 |
PCD2M150_#D1 |
0D1 |
PCD2.M170 |
PCD2M170_#21.blk |
021 |
PCS1.C88x |
PCS1.C6xx_C8xx__#B3 |
0B3 |